What's Wrong Here?
Dec 1, 2008 12:00 PM, By Joe Tedesco, NEC Columnist
How well do you know the Code? Think you can spot violations the original installer either ignored or couldn't identify? Here's your chance to moonlight as an electrical inspector and second-guess someone else's work from the safety of your living room or office. Can you identify the Code violation(s) in this photo?
Hint: Now you see it — now you don't.
October Winners
Our three winners this month were: Khondker Ahmed, electrical engineer III, New York City Transit, Broadway, N.Y.; Aaron Beatty, electrical engineer/project manager, Professional Consultants, Inc., Evansville, Ind.; and James E. Young, P.E., project manager, Washington Group International, Inc., Denver.
Here's a list of some of the Code sections they felt were in violation.
As per 590.4(F), “All lamps for general illumination shall be protected from accidental contact or breakage by a suitable luminaire or lampholder with a guard.”
Two references can also be made on the damp or wet location front. As per 410.10(A), “Luminaires installed in wet or damp locations shall be installed such that water cannot enter or accumulate in wiring compartments, lampholders, or other electrical parts.” As per 410.96, “Lampholders installed in wet or damp locations shall be of the weatherproof type.”
If this installation was made for temporary reasons or done so in conjunction with a decorative lighting display then the time constraint requirements of 590.3 would also come into play.
‘TELL THEM WHAT THEY'VE WON…’
Using the 2008 NEC, correctly identify the Code violation(s) in this month's photo — in 200 words or less — and you could win something to put in your toolbox. E-mail your response to electrical.group@penton.com, and we'll select three winners (excluding manufacturers and prior winners) at random from the correct submissions. Winners will receive a set of insulated hand tools from Ideal Industries, Inc. valued at more than $125.* The set includes 9.25-inch insulated side-cutting pliers, 10-inch insulated tongue-and-groove pliers, and a 0.25-inch × 6-inch insulated screwdriver.
* Please allow six to eight weeks for delivery of tools.
Want to use this article? Click here for options!
© 2012 Penton Media, Inc.
Code Challenge
Code Quiz
Feb 2, 2012 9:02 PM, By Steven Owen
When installing audio distribution cables exposed on the surface of ceilings and sidewalls, the cables shall be supported by which of the following products?
- ...
More Code Quizzes
Code Q&A
Feb 2, 2012 8:58 PM, By Mike Holt
Q. Is it acceptable to use a 14 AWG conductor for the bonding jumper to a receptacle on a 20A branch circuit?
...
More Code Q&As
Acceptable Use Policy blog comments powered by Disqus
advertisement
product spotlight
Labeling tool
Feb 10, 2012 7:58 AM
The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.



































