What's Wrong Here?

Dec 3, 2009 11:43 AM, By Brian J. McPartland, NEC Consultant

Hint: Raceway-supported box

This photo shows an all-too-common installation mistake: An outdoor box supported by a single raceway. This particular installation is an obvious and clear violation of 314.23.

The third sentence in 314.23(F), which covers raceway-supported enclosures that are providing support for devices and/or fixtures, says "It (i.e., the box) shall be supported by two or more conduits threaded wrenchtight into the enclosure or hubs." The next sentence indicates that "Each conduit shall be supported within 450mm (18 in.) of the enclosure." Although the requirement given in the third sentence of 314.23(F) for raceway-support of an outlet box has been met, the rule presented by the second sentence — use of two conduits threaded into the box or hubs — has not.

It should be noted that raceway support of outlet, device, junction, and pull boxes has long been permitted by the NEC, but with certain restrictions. In addition, use of the raceway-supported box to provide support for devices and fixtures has also been acceptable for some time. In this photo, we see an outlet box-mounted incandescent flood light and a photoelectric switch that controls the light, which is specifically permitted by the Code, but only in accordance with the rules of 314.23(F).

The first sentence of part (F) in 314.23 states, "An enclosure that contains a device(s), other than splicing devices, or supports a luminaire(s), lampholder or other equipment and is supported by entering raceways shall not exceed 1,650 cm3 (100 in3) in size." This application meets that stipulation, but the wording used in that sentence actually recognizes the use of an outlet box to support more than one device and/or fixture, provided the box is not more than 100 in3. However, a certain amount of common sense must be exercised when applying this rule. Obviously, the number and size of devices and/or fixtures should be limited to ensure the box, which may be no more 100 in3 to satisfy the specific verbiage used in 314.23(F), is capable of actually providing support for the attached equipment. This is a different approach that the Code takes when dealing with ceiling and wall outlet boxes that support fixtures as covered in 314.27(A).

In part (A) of 314.27, the NEC requires that ceiling-mounted outlet boxes supporting fixtures "shall be designed for the purpose and shall be required to support a luminaire (fixture) weighing a minimum of 23 kg (50 lb)." For wall-mounted outlet boxes, the Code places the same mandate on the design of the box. As we have seen, for raceway-supported boxes that are providing support for devices and fixtures, there is no limitation on the number or size of the attached equipment, which essentially requires the installer and inspector to determine the "maximum" number and size of devices and fixtures.

> Try Another Quiz

Want to use this article? Click here for options!

Code Challenge

Code Quiz

May 10, 2012 12:29 PM, By Steven Owen, National Code Seminars

When installing a shielded cable or a twisted pair cable in a Class I, Division 1 location where a cable seal is required, when is it not required to remove the shielding material or separate the twisted pairs of those type cables?...


More Code Quizzes

Code Q&A

May 24, 2012 10:42 AM, By Mike Holt, NEC Consultant

Q. What labeling does the Code require in regard to arc flash hazard warning?...


More Code Q&As
 



Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

May 10, 2012 12:44 PM

What's Wrong Here?

Apr 19, 2012 10:09 AM

What's Wrong Here?

Apr 5, 2012 2:27 PM

View all What's Wrong Here?

product spotlight

EV charger tester

May 25, 2012 8:26 AM

EV charger tester

The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M Whitepaper

Arc Mitigation –A Three-Step Approach

Did you know that an arc-flash incident hospitalizes 5-7 workers per day in North America, severely impacting processes and profitability with lost production? Download This Sponsored Whitepaper Today!

What's New in Residential Cabling?
Date: Wednesday, May 30, 2012
Time: 2:00pm ET


In this The Home Depot sponsored Low Voltage Webinar, Ron Kipper RCDD / NTS will discuss the need for compression style coaxial connectors and the migration of the entire CATV, Satellite and Audio / Video industry to them. Register Today!

Grounding Versus Bonding
Now Available On-Demand


In this 60-minute FREE webinar, Mike Holt of Mike Holt Enterprises, Inc. will explain the purpose of grounding and bonding as related to the most current requirements set forth in the 2011 NEC. Register to View On-Demand!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues