What's Wrong Here?
Oct 24, 2005 4:01 PM, By Joe Tedesco
Answer:
Hint: Cool splice for an air conditioner, huh?
The requirements of Art. 440, Part VII, cover electrically energized room air conditioners that control temperature and humidity (with or without provisions for heating). These units are considered to be an AC appliance of the air-cooled window, console, or in-wall type if they’re installed in the conditioned room and incorporate a hermetic refrigerant motor-compressor(s). The requirements of this Article apply to equipment rated 250V or less, single phase. This equipment shall be permitted to be cord-and-attachment-plug-connected. (440.60)
Where a flexible cord is used to supply a room air conditioner of this type, the length of such cord cannot exceed 3 meters (10 feet) for a nominal 120V rating or 1.8 meters (6 feet) for a nominal 208V or 240V rating. (440.64)
The branch circuit requirements for these units [440.62(A)] state that a room air conditioner is considered as a single motor unit in determining its branch-circuit requirements where all the following conditions are met: (1) It is cord-and-attachment-plug-connected. (2) Its rating is not more than 40A and 250V, single phase.
In addition, as per 440.63, an attachment plug and receptacle is permitted to serve as the disconnecting means for a single-phase room air conditioner rated 250V or less, if the manual controls on the room air conditioner are readily accessible and located within 1.8 meters (6 feet) of the floor.
And last, but not least, single-phase cord-and-plug-connected room air conditioners are required to be provided with factory-installed leakage current detection and interruption (LCDI) and arc fault circuit interrupter (AFCI) protection as an integral part of the attachment plug, or be located in the power supply cord within 300 millimeters (12 inches) of the attachment plug. (440.65)
Want to use this article? Click here for options!
© 2012 Penton Media, Inc.
Code Challenge
Code Quiz
May 10, 2012 12:29 PM, By Steven Owen, National Code Seminars
When installing a shielded cable or a twisted pair cable in a Class I, Division 1 location where a cable seal is required, when is it not required to remove the shielding material or separate the twisted pairs of those type cables?...
More Code Quizzes
Code Q&A
May 24, 2012 10:42 AM, By Mike Holt, NEC Consultant
Q. What labeling does the Code require in regard to arc flash hazard warning?...
More Code Q&As
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
What's Wrong Here?
May 10, 2012 12:44 PM
View all What's Wrong Here?
What's Wrong Here
Sponsored By:
product spotlight
EV charger tester
May 25, 2012 8:26 AM
The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.