What's Wrong Here?
Sep 24, 2009 1:13 PM, Brian J. McPartland, NEC Consultant
Hint: Is that really Romex?
Isn't this beautiful? In this photo, we see a temporary wiring setup where the installer apparently fabricated some cable assemblies with plug caps for that purpose. As given in 334.10(A)(1), Type NM cable (Romex) may be used "for both exposed and concealed work in normally dry locations except as prohibited by 334.10(3)." Here, the use of Type NM cable outdoors at this temporary wiring installation is a clear violation of 334.10(A)(1), simply because such a location cannot be construed as being "normally dry."
An additional concern about this installation is related to the fact that the installer fabricated these temporary wiring cables with plug caps. Although such fabrication is not prohibited by the rules given for temporary wiring in Art. 590, other rules governing the use of the specific wiring methods must also be satisfied, which was not done in this case. The manner in which the plug caps are installed is questionable, at best. It seems as if this is a violation of 110.12, which requires that "electrical equipment shall be installed in a neat and workmanlike manner." This rule has been interpreted in the past to apply to the assembly of electrical equipment as well as the installation of the equipment.
It should be noted that while not prohibited, use of homemade assemblies such as these should be minimized and employed only as a last resort. There are many different types of commercially available temporary wiring cables that are listed for this specific purpose. And while not prohibited by the NEC, it should be noted that the Occupational Safety and Health Administration (OSHA) would consider the use of homemade temporary wiring cables a violation of the Electrical Design Safety Standard. In general, OSHA requires that where a listed version of any product exists, the listed product must be used. That requirement is more restrictive than the NEC's rules on the use of listed equipment for temporary wiring. The only item specifically required to be listed in Art. 590 is decorative lighting, as given in 590.5.
Want to use this article? Click here for options!
© 2012 Penton Media, Inc.
Code Challenge
Code Quiz
May 10, 2012 12:29 PM, By Steven Owen, National Code Seminars
When installing a shielded cable or a twisted pair cable in a Class I, Division 1 location where a cable seal is required, when is it not required to remove the shielding material or separate the twisted pairs of those type cables?...
More Code Quizzes
Code Q&A
May 24, 2012 10:42 AM, By Mike Holt, NEC Consultant
Q. What labeling does the Code require in regard to arc flash hazard warning?...
More Code Q&As
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
What's Wrong Here?
May 10, 2012 12:44 PM
View all What's Wrong Here?
What's Wrong Here
Sponsored By:
product spotlight
EV charger tester
May 25, 2012 8:26 AM
The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.