What's Wrong Here?

Sep 10, 2009 6:27 PM, Brian J. McPartland, NEC Consultant

Hint: Was the installer color blind?

In this particular installation, you can plainly see two conductors that have "white" insulation being used as phase conductors. This is a clear violation of 200.7, which limits the use of the color white "only to grounded circuit conductors, unless otherwise permitted in 200.7(B) or (C)."

Given that these conductors are operating at 120VAC, the rule of 200.7(B), which covers systems operating at less than 50V does not apply. And while there is limited permission for a conductor other than the grounded conductor to be colored "white," re-identification of the white insulated conductor is required. As noted in 200.7(C)(1), "If part of a cable assembly and where re-identified to indicate its use as an ungrounded conductor, by painting or other effective means at its termination, and at each location where the conductor is visible and accessible." This re-identification must completely encircle the conductor and be "a color other than white, gray, or green." Otherwise, such use of a white-colored conductor is a clear violation of the Code.

Another potential violation is the termination of two conductors under a single terminal. Such application is a violation of 110.3(B), which mandates all equipment to be used in accordance with any instructions given with the listing or labeling. This rule essentially and effectively makes all instructions given in the Underwriters Laboratories (UL) Directories — the so-called White Book, Green Book, Red Book, and Orange Book — part of the NEC. UL has long indicated in its general requirements that all listed terminating devices are suited for one conductor only, unless otherwise indicated. Although there is no way to know if this breaker's connection points are so listed without being able to fully identify the manufacturer and model number, my suspicion is it is not.

The last concern is related to the ampere rating of the breaker with two conductors terminated under a single terminal. These 12 AWG conductors are woefully under protected by the 60A breaker, even if this were a motor circuit.

> Try Another Quiz

Want to use this article? Click here for options!

Code Challenge

Code Quiz

Feb 2, 2012 9:02 PM, By Steven Owen

When installing audio distribution cables exposed on the surface of ceilings and sidewalls, the cables shall be supported by which of the following products?

    ...


More Code Quizzes

Code Q&A

Feb 2, 2012 8:58 PM, By Mike Holt

Q. Is it acceptable to use a 14 AWG conductor for the bonding jumper to a receptacle on a 20A branch circuit?

...


More Code Q&As
 



Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

Feb 2, 2012 7:54 PM

What's Wrong Here?

Jan 19, 2012 4:06 PM

What's Wrong Here?

Jan 5, 2012 11:53 AM

View all What's Wrong Here?

product spotlight

Labeling tool

Feb 10, 2012 7:58 AM

Labeling tool

The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M TV

Arlington CP9000

Arlington's new 9" diameter ceiling cover plate is the neatest way to cover unused "high hat" cans. With no tools needed, installation couldn't be faster!...

Arlington Gangable Boxes

Designed for new or retrofit applications, these snap-together gangable plastic boxes eliminate the need to construct a multiple-gang steel box out of several individual ones...

Understanding NEC Requirements for Solar Photovoltaic Systems
During this session, Mike Holt will address possible conflicts or confusing NEC requirements, provide tips on proper electrical installation techniques, and discuss the dangers related to improper installations. View this On Demand Webinar!



resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues