What's Wrong Here?
Aug 12, 2010 12:02 PM, By Brian J. McPartland
Hint: Water, water everywhere
This is one of those situations where the actual problem "came out in the wash" — that is, there is no way for an inspector to determine that this type of deterioration would occur at the time of the original final inspection. However, we can clearly see this is a violation of 110.11, which in part states, "Unless identified for use in the operating environment, no conductors or equipment shall be located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that have a deteriorating effect on the conductors or equipment; or where exposed to excessive temperatures."
Further analysis reveals this service equipment is located indoors and is fed from an overhead service. Maybe if the installer had sealed the raceways as required by 300.5(G) — which is only specifically applicable to underground applications — then, quite possibly, the equipment would not have ended up in this state. Although the requirements of 230.53 call for service raceways to be "arranged to drain," I'm quite certain the Code writers did not intend for them to drain into the service equipment.
Due to the nature of enforcement, unless an inspector were to see the condition of this service switch during the course of an inspection on another part of the premises, there really is no means available to require the property owner to replace this deteriorated equipment. And, as we all know, trying to tell the property owner that his service equipment is in bad repair is like trying to tell your buddy that his sister is not attractive. They just don't see it, and are offended by your suggestion.
Want to use this article? Click here for options!
© 2012 Penton Media, Inc.
Code Challenge
Code Quiz
May 10, 2012 12:29 PM, By Steven Owen, National Code Seminars
When installing a shielded cable or a twisted pair cable in a Class I, Division 1 location where a cable seal is required, when is it not required to remove the shielding material or separate the twisted pairs of those type cables?...
More Code Quizzes
Code Q&A
May 24, 2012 10:42 AM, By Mike Holt, NEC Consultant
Q. What labeling does the Code require in regard to arc flash hazard warning?...
More Code Q&As
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
What's Wrong Here?
May 10, 2012 12:44 PM
View all What's Wrong Here?
What's Wrong Here
Sponsored By:
product spotlight
EV charger tester
May 25, 2012 8:26 AM
The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.