What's Wrong Here?

Jul 23, 2004 12:45 PM, By Joe Tedesco

Photo 1





















A reader submitted these pictures of a chiller served by a feeder that consists of three sets of 350 kcmil THHN conductors that originate at an 800A breaker in a switchgear room, extending about 600 feet to the side of the building. The conductors terminate at the outdoor chiller enclosure main breaker. Most of the feeder conductor is routed in a cable tray, the last 40 feet of which is in rigid metal conduit (Photo 1). There’s also a short section of liquidtight flexible metal conduit located outdoors.

By the submitter’s calculation, the voltage drop for this circuit (with a load of 300A) should only be about 3.9V. However, he measured a voltage drop in the conductor of 15V. The excessive voltage drop is due to higher impedance of the circuit.

Photo 2. Feeder termination arrangement at chiller main breaker.

Three raceways carry the three sets of conductors (Photo 2). However, all the “phase A” conductors are in one raceway, all the “phase B” conductors are together, and all the “phase C “ conductors are together. Along with excessive voltage drop and unbalanced current between phases, the most dramatic consequence observed is induction heating of the metal conduits (Photo 3).


See 310.4 (no Exceptions apply) for the rules of installation of conductors in parallel:

Photo 3. At a load current of only 300A, the side of the conduit registers 52°C (125°F). This is actually too hot to hold your hand on for any length of time.

“Aluminum, copper-clad aluminum, or copper conductors of size 1/0 AWG and larger, comprising each phase, neutral, or grounded circuit conductor, shall be permitted to be connected in parallel (electrically joined at both ends to form a single conductor).

“The paralleled conductors in each phase, neutral, or grounded circuit conductor shall:

“(1) Be the same length
(2) Have the same conductor material
(3) Be the same size in circular mil area
(4) Have the same insulation type
(5) Be terminated in the same manner

“Where run in separate raceways or cables, the raceways or cables shall have the same physical characteristics. Conductors of one phase, neutral, or grounded circuit conductor shall not be required to have the same physical characteristics as those of another phase, neutral, or grounded circuit conductor to achieve balance.

“FPN: Differences in inductive reactance and unequal division of current can be minimized by choice of materials, methods of construction, and orientation of conductors.

“Where equipment-grounding conductors are used with conductors in parallel, they shall comply with the requirements of this section except that they shall be sized in accordance with 250.122.

“Conductors installed in parallel shall comply with the provisions of 310.15(B)(2)(a).”

The submitter also noted many other violations, including:
• The raceways were not bonded to the enclosure.
• The equipment grounding conductor was missing from two of the three raceways.
• The small pump unit sub-feeder conductors tapped onto the line side of breaker aren’t protected against overcurrent.
• The equipment grounding conductor appears smaller than that required by Table 250.122.
• The conduits aren’t bonded to cable tray.
• The phase conductors aren’t grouped together in cable tray.
• The equipment grounding conductor isn’t grouped together with phase conductors.

Want to use this article? Click here for options!

Code Challenge

Code Quiz

Mar 11, 2010 12:45 PM, By Steven Owen

When installing outlet boxes for wall-mounted luminaires, when can you use No. 6 screws to secure the luminaire yoke to a plaster ring?...


More Code Quizzes

Code Q&A

Mar 11, 2010 12:48 PM, By Mike Holt

Q. Can a receptacle be used as a splicing device?...


More Code Q&As
 



Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

Whats Wrong Here?

Mar 11, 2010 12:54 PM

What's Wrong Here?

Feb 18, 2010 5:04 PM

What's Wrong Here?

Feb 4, 2010 5:06 PM

View all What's Wrong Here?

product of the week

CAD Software

March 15, 2010

CAD Software

View all 2010 Products of the Week

Shocking Stats

54
More Industry Statistics

Recent Comments

More...




Professionals provide answers to your questions. Become an expert!


EC&M TV

Arlington CED1 Entrance Hoods

The Scoop Series CED Entrance Plates and Hoods are reversible, non-metallic, single and two-gang versions...

Southwire's 2009 Cable Innovation Road Show

Gain years worth of insight with Southwire’s 2009 Cable Innovation Road Show with Grounding Seminar!

George Brown College

Online Tech Training – Electronics, PLC, and Robotics programs at George Brown College.

 

Listen
Sizing Gen-Sets: Facts, Hints, and Good Judgment
Listen

The complexities of today’s commercial or industrial facility, with their equipment environment of linear and nonlinear loads, places a whole new light on sizing engine-generator sets.

Arc Mitigation - A Total System Approach
There’s no question the risk of arc flash hazards is real in the electrical industry. What many don’t always realize is the impact in business interruption from such events typically far outweighs the physical damage to equipment. View this On Demand Webinar!

Implementing an Industrial Ethernet Infrastructure that's Built to Last
This webinar explores the key benefits of implementing a robust complete, end-to-end Industrial Ethernet solution – from cabling and connectivity, to active components and associated hardware. View this On Demand Webinar!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues