What's Wrong Here?

Jul 17, 2008 11:24 PM, By Joe Tedesco, NEC Columnist

Hint: Upgrade equals disaster

”We were asked to do a load test on a standby generator,” says Paul Ryan of Paul A. Ryan, Inc., Wicomico Church, Va. “I ended up making a jaw-dropping discovery.”

“This service upgrade was made approximately eight years ago. They converted a 320A overhead feed to a 600A underground feed with a pedestal-mounted CT cabinet. Rather than change the service conductors, they used the old wall-mounted meter pan and cover (with a plastic meter blank) as a J-box. To make matters worse, the old overhead mast was unbolted and left loose from the top of the meter pan, allowing rain water to cascade over the connections within. An antenna guide wire was even tied to the top of the mast.

“With only one wall strap keeping the mast upright, every time the wind blew, the abandon mast conductors pushed on the hot conductors in the meter pan. If you look to the left, you’ll see where one of the split bolt legs blew a hole through the cover.

“After bringing this to the attention of building manager, we were contracted to correct this mess of violations. We left it Code compliant, of course.”

I can’t find anything here that would allow this to be done. Section 110.3 focuses on the examination, identification, installation, and use of equipment.

110.3(A) states, “In judging equipment, considerations such as the following shall be evaluated:”

  1. “Suitability for installation and use in conformity with the provisions of this Code FPN: Suitability of equipment use may be identified by a description marked on or provided with a product to identify the suitability of the product for a specific purpose, environment, or application. Suitability of equipment may be evidenced by listing or labeling.
  2. ”Mechanical strength and durability, including, for parts designed to enclose and protect other equipment, the adequacy of the protection thus provided
  3. ”Wire-bending and connection space
  4. ”Electrical insulation
  5. ”Heating effects under normal conditions of use and also under abnormal conditions likely to arise in service
  6. ”Arcing effects
  7. ”Classification by type, size, voltage, current capacity, and specific use
  8. ”Other factors that contribute to the practical safeguarding of persons using or likely to come in contact with the equipment”
110.3(B) states, “Listed or labeled equipment shall be installed and used in accordance with any instructions included in the listing or labeling.”

I also believe that abandoned wiring of all types should be removed.

> Try Another Quiz

Want to use this article? Click here for options!

Code Challenge

Code Quiz

May 10, 2012 12:29 PM, By Steven Owen, National Code Seminars

When installing a shielded cable or a twisted pair cable in a Class I, Division 1 location where a cable seal is required, when is it not required to remove the shielding material or separate the twisted pairs of those type cables?...


More Code Quizzes

Code Q&A

May 24, 2012 10:42 AM, By Mike Holt, NEC Consultant

Q. What labeling does the Code require in regard to arc flash hazard warning?...


More Code Q&As
 



Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

May 10, 2012 12:44 PM

What's Wrong Here?

Apr 19, 2012 10:09 AM

What's Wrong Here?

Apr 5, 2012 2:27 PM

View all What's Wrong Here?

product spotlight

EV charger tester

May 25, 2012 8:26 AM

EV charger tester

The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M Whitepaper

Arc Mitigation –A Three-Step Approach

Did you know that an arc-flash incident hospitalizes 5-7 workers per day in North America, severely impacting processes and profitability with lost production? Download This Sponsored Whitepaper Today!

What's New in Residential Cabling?
Date: Wednesday, May 30, 2012
Time: 2:00pm ET


In this The Home Depot sponsored Low Voltage Webinar, Ron Kipper RCDD / NTS will discuss the need for compression style coaxial connectors and the migration of the entire CATV, Satellite and Audio / Video industry to them. Register Today!

Grounding Versus Bonding
Now Available On-Demand


In this 60-minute FREE webinar, Mike Holt of Mike Holt Enterprises, Inc. will explain the purpose of grounding and bonding as related to the most current requirements set forth in the 2011 NEC. Register to View On-Demand!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues