What's Wrong Here?
Apr 8, 2010 4:36 PM, By Brian J. McPartland, NEC Consultant
Hint: Receptacle configuration
This photo shows a violation of the rule given in 406.11. This new requirement was added to the 2008 version of the NEC. It requires all receptacles covered by 210.52 to be tamper-resistant. The GFCI receptacle in this new bathroom is not of the tamper-resistant type.
406.11 simply and succinctly says, "In all areas specified in 210.52, all 125-volt, 15 and 20 ampere receptacles shall be listed tamper-resistant receptacles." Full understanding of the widespread and all encompassing nature of this change becomes apparent when one reviews the rules given in 210.52.
As most are aware, 210.52 provides a variety of requirements related to dwelling unit receptacle outlets. This section states where, when, and how many receptacles must be located in virtually all rooms, spaces, and areas within a dwelling unit. Additionally, it identifies those receptacles that may not be considered as satisfying the rule of this section, which is essentially intended to ensure that there is an adequate number of accessible receptacle outlets available in habitable rooms to minimize the need for extension cords and/or plug strips within a dwelling unit.
210.52 also gives requirements for receptacle outlets in those dwelling unit rooms and areas that would not be viewed as "habitable rooms," such as the basement, kitchen, garage, etc., and bathrooms, which is covered in part (D) of 210.52.
It should be noted that while 210.52(D) only requires one 15A or 20A, 125V receptacle within 3 ft of each sink in the bathroom, the requirement in 210.8(A)(1), which calls GFCI protection of receptacles in dwelling unit bathrooms, would apply to all 15A and 20A, 125V receptacles in a dwelling unit bathroom, and GFCI protection must be provided for any such receptacle installed there. When combined with the rule of 406.11, any 15A or 20A, 125V-rated receptacle installed in a dwelling unit bathroom would have to be GFCI protected and be a listed tamper-resistant receptacle.
Want to use this article? Click here for options!
© 2012 Penton Media, Inc.
Code Challenge
Code Quiz
May 10, 2012 12:29 PM, By Steven Owen, National Code Seminars
When installing a shielded cable or a twisted pair cable in a Class I, Division 1 location where a cable seal is required, when is it not required to remove the shielding material or separate the twisted pairs of those type cables?...
More Code Quizzes
Code Q&A
May 24, 2012 10:42 AM, By Mike Holt, NEC Consultant
Q. What labeling does the Code require in regard to arc flash hazard warning?...
More Code Q&As
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
What's Wrong Here?
May 10, 2012 12:44 PM
View all What's Wrong Here?
What's Wrong Here
Sponsored By:
product spotlight
EV charger tester
May 25, 2012 8:26 AM
The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.