ECM Buyers' Guide
 

Whats Wrong Here?

Mar 11, 2010 12:54 PM, By Brian J. McPartland, NEC Consultant

Hint: Size of feeder conductor

Surprise! There is no violation here because the 4/0 aluminum Type SE feeder cable shown is installed outdoors. However, if the SE cable supplying the meters on the load side of the service disconnect (which, by definition, makes this cable a feeder) was also installed indoors, it would be a violation of 338.10(B)(4)(a), which covers the use of SE cable as feeders and branch circuits indoors.

In the 2005 NEC, the requirements of 338.10(B)(4)(a) stated, "In addition to the provisions of this article, Type SE service-entrance cable used for interior wiring shall comply with the installation requirements of Parts I and II of Article 334, excluding 334.80." Here the Code is essentially requiring Type SE cable to be treated as if it were Type NM cable when used indoors as feeders and branch circuits. However, the exclusion of 334.80, which deals with the ampacity of Type NM cable, means that the ampacity of the Type SE cable conductors would be determined in accordance with 310.15 and its accompanying tables.

In the 2008 Code, the 334.80 reference was eliminated. The wording of 338.10(B)(4)(a) now reads as follows, "In addition to the provisions of this article, Type SE service-entrance cable used for interior wiring shall comply with the installation requirements of Parts I and II of Article 334." The new wording now requires compliance with all rules in Art. 334, including the ampacity requirements of 334.80.

The part of 334.80 that presents potential problems for installers is the second sentence. It says, "The ampacity shall be in accordance with the 60°C (140°F) conductor temperature rating." This means for a given wire size the ampacity of the SE cable conductors must never be greater than the value shown in the left-hand 60°C column of Table 310.16. So, if the SE cable exiting the service disconnect were run into the building it would not be permitted to be the same size as service entrance conductors supplying the service disconnect.

For example, 4/0 aluminum (which has an ampacity of 180A at 75°C, as noted in Table 310.16) is properly protected by a 200A disconnect and would be permitted to supply this 200A service. However, at 60°C, 4/0 aluminum has an ampacity of only 150A. Therefore, if the feeder supplying the meter bank were run inside the building it would have to be of a size that is properly protected by a 200A circuit breaker. In this case, the smallest sized aluminum conductor that would be permitted is 300kcmil. If 4/0 copper conductor was used here it would comply with the requirements of the Code.

With all this being said, remember that for one- and two-family dwelling units, the rule of 310.15(B)(6) would permit running a 4/0 aluminum conductor into the building, because this rule applies to both the service entrance conductors supplying the service disconnect and the "feeder conductors that serve as the main power feeder."

Keep these subtle changes in mind whenever running SE cable as feeders indoors. If you are not covered by the rule of 310.15(B)(6), then the size of any such feeder would have to have an ampacity in the 60°C column that is properly protected by the service disconnecting means.

> Try Another Quiz

Want to use this article? Click here for options!

Code Challenge

Code Quiz

Feb 2, 2012 9:02 PM, By Steven Owen

When installing audio distribution cables exposed on the surface of ceilings and sidewalls, the cables shall be supported by which of the following products?

    ...


More Code Quizzes

Code Q&A

Feb 2, 2012 8:58 PM, By Mike Holt

Q. Is it acceptable to use a 14 AWG conductor for the bonding jumper to a receptacle on a 20A branch circuit?

...


More Code Q&As
 



Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

Feb 2, 2012 7:54 PM

What's Wrong Here?

Jan 19, 2012 4:06 PM

What's Wrong Here?

Jan 5, 2012 11:53 AM

View all What's Wrong Here?

product spotlight

Labeling tool

Feb 10, 2012 7:58 AM

Labeling tool

The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M TV

Arlington CP9000

Arlington's new 9" diameter ceiling cover plate is the neatest way to cover unused "high hat" cans. With no tools needed, installation couldn't be faster!...

Arlington Gangable Boxes

Designed for new or retrofit applications, these snap-together gangable plastic boxes eliminate the need to construct a multiple-gang steel box out of several individual ones...

Understanding NEC Requirements for Solar Photovoltaic Systems
During this session, Mike Holt will address possible conflicts or confusing NEC requirements, provide tips on proper electrical installation techniques, and discuss the dangers related to improper installations. View this On Demand Webinar!



resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues