What's Wrong Here?

Feb 18, 2010 5:04 PM, By Brian J. McPartland, NEC Consultant

Hint: Deteriorating agents

This photo appears to show a violation of the requirements set forth in 110.11, which says, "Equipment not identified for outdoor use and equipment identified only for indoor use, such as 'dry locations,' 'indoor use only,' 'damp locations,' or enclosure Types 1, 2, 5, 12, 12K and/or 13, shall be protected against permanent damage from weather during building construction." The reason I say this appears to be a violation is it seems logical that if the cable sheath were to rust — as a result of exposure to the weather and outdoor elements — then this would constitute "permanent damage."

But what if the conductors oxidized during this exposure period? If they did, and you were able to remove the oxidation from the conductors, then one would assume such damage would not be considered "permanent." Therefore, there would not be a violation of this rule. But is such remedial action recognized as returning the conductors to their original condition, or does any such degradation mean the cable would have to be replaced?

The Code gives no guidance on this matter. However, while the NEC does not address the concerns stated here, the National Electrical Manufacturers' Association (NEMA) did publish a technical paper on water-damaged equipment and conductors back in 2006. The press release announcing the paper indicates that water-damage equipment and conductors pose a potential danger if reenergized without remediation of some sort. Additionally, it goes on to state where equipment or conductors are exposed to water, they may or may not be able to be reconditioned, but such determination should be made in consultation with the equipment manufacturer. This press release also admonishes electrical distributors from selling water-damaged equipment and conductors.

While the press release is useful, inasmuch as it alerts one to the potential for danger, the paper itself provides more detailed guidance on what should be done under different scenarios. It is a very useful document you should be familiar with. A copy of the paper can be downloaded free of charge.

Although the above referenced technical paper can provide extremely useful guidance when dealing with water damaged equipment and conductors, it seems the best way to deal with this matter is to prevent such exposure in the first place. In this situation, if the coils shown in the photo were stored in plastic garbage bags, or were secured to the overhead and protected from the elements, then there would be no need for concern.

> Try Another Quiz

Want to use this article? Click here for options!

Code Challenge

Code Quiz

May 10, 2012 12:29 PM, By Steven Owen, National Code Seminars

When installing a shielded cable or a twisted pair cable in a Class I, Division 1 location where a cable seal is required, when is it not required to remove the shielding material or separate the twisted pairs of those type cables?...


More Code Quizzes

Code Q&A

May 24, 2012 10:42 AM, By Mike Holt, NEC Consultant

Q. What labeling does the Code require in regard to arc flash hazard warning?...


More Code Q&As
 



Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

May 10, 2012 12:44 PM

What's Wrong Here?

Apr 19, 2012 10:09 AM

What's Wrong Here?

Apr 5, 2012 2:27 PM

View all What's Wrong Here?

product spotlight

EV charger tester

May 25, 2012 8:26 AM

EV charger tester

The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M Whitepaper

Arc Mitigation –A Three-Step Approach

Did you know that an arc-flash incident hospitalizes 5-7 workers per day in North America, severely impacting processes and profitability with lost production? Download This Sponsored Whitepaper Today!

What's New in Residential Cabling?
Date: Wednesday, May 30, 2012
Time: 2:00pm ET


In this The Home Depot sponsored Low Voltage Webinar, Ron Kipper RCDD / NTS will discuss the need for compression style coaxial connectors and the migration of the entire CATV, Satellite and Audio / Video industry to them. Register Today!

Grounding Versus Bonding
Now Available On-Demand


In this 60-minute FREE webinar, Mike Holt of Mike Holt Enterprises, Inc. will explain the purpose of grounding and bonding as related to the most current requirements set forth in the 2011 NEC. Register to View On-Demand!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues