ECM Buyers' Guide
 

What's Wrong Here?

Feb 4, 2010 5:06 PM, By Brian J. McPartland, NEC Consultant

Hint: Field markings

Although not completely clear in this photo, this installation is at a commercial occupancy. As a result, it shows a clear violation of 110.16, which calls for the field marking of certain pieces of equipment to alert operations/maintenance personnel of a potential arc flash hazard.

The requirement of 110.16 says, "Electrical equipment, such as switchboards, panelboards, industrial control panels, meter socket enclosures, and motor control centers, that are in other than dwelling occupancies — and are likely to require examination, adjustment, servicing, or maintenance while energized — shall be field marked to warn qualified persons of potential electric arc flash hazards. The marking shall be located so as to be clearly visible to qualified persons before examination, adjustment, servicing, or maintenance of the equipment."

There is no question that this meter can would be required to have an arc flash "warning label" to satisfy 110.16, but what about the disconnects? Are they required to be marked? It doesn't appear so, as disconnects are not specifically mentioned in the first sentence of this Code section.

Here's another question that comes to mind with regard to satisfying this rule. If, for example, there were two panelboards (one on either side of the inverter) at this location, would all three pieces of equipment have to be marked with an arc flash warning label, or would a single label on the meter can be enough to satisfy this labeling requirement? My interpretation is that all three pieces of equipment would have to be marked. Even though "qualified persons" should be knowledgeable enough to understand that if the meter can is marked, then the equipment on either side of it has the same potential for such a hazard.

Field markings are critical elements for safety. There are a good number of field markings required by the Code — from circuit directories to series combination rated overcurrent protection to warning labels. It has also been adjudicated that for every Code-required warning label, the label must identify the hazard and give direction with regard to the action that must be taken. For example, with an arc-flash warning label, the sign should say something like, "Arc Flash Hazard. Proper Personnel Protective Equipment Required." This type of warning sign would serve to completely satisfy both the Code rule and the legal criteria that have been established for any Code-required warning label.

Lastly, it should be noted the courts have established that if more than one language is spoken by operations/maintenance personnel at the occupancy in question, then the warning label(s) must be provided in all of the languages spoken. The courts have indicated that failure to provide warning signs in the languages(s) spoken by operations and maintenance persons on the premises is the same as not providing a sign.

> Try Another Quiz

Want to use this article? Click here for options!

Code Challenge

Code Quiz

Feb 2, 2012 9:02 PM, By Steven Owen

When installing audio distribution cables exposed on the surface of ceilings and sidewalls, the cables shall be supported by which of the following products?

    ...


More Code Quizzes

Code Q&A

Feb 2, 2012 8:58 PM, By Mike Holt

Q. Is it acceptable to use a 14 AWG conductor for the bonding jumper to a receptacle on a 20A branch circuit?

...


More Code Q&As
 



Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

Feb 2, 2012 7:54 PM

What's Wrong Here?

Jan 19, 2012 4:06 PM

What's Wrong Here?

Jan 5, 2012 11:53 AM

View all What's Wrong Here?

product spotlight

Labeling tool

Feb 10, 2012 7:58 AM

Labeling tool

The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M TV

Arlington CP9000

Arlington's new 9" diameter ceiling cover plate is the neatest way to cover unused "high hat" cans. With no tools needed, installation couldn't be faster!...

Arlington Gangable Boxes

Designed for new or retrofit applications, these snap-together gangable plastic boxes eliminate the need to construct a multiple-gang steel box out of several individual ones...

Understanding NEC Requirements for Solar Photovoltaic Systems
During this session, Mike Holt will address possible conflicts or confusing NEC requirements, provide tips on proper electrical installation techniques, and discuss the dangers related to improper installations. View this On Demand Webinar!



resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues