Whats Wrong Here?
Jan 21, 2010 4:40 PM, Brian J. McPartland, NEC Consultant
Hint: Think clearances
Although it might be a little hard to see, the exposed conductors of the SE cable are too close to the window, which is a violation of the rules given in 230.9. This section states, "Service conductors installed as open conductors or multi-conductor cable without an overall outer jacket shall have a clearance of not less than 900 mm (3 ft) from windows that are designed to be opened, doors, porches, balconies, ladders, stairs, fire escapes, or similar locations." The exposed conductors on the side of this building are secured to the siding within 3 ft of the window.
The basic concept is to keep the open service conductors far enough away from the window to prevent someone from accidently, or, to a certain extent, intentionally coming in contact with them. The other locations identified (i.e., doors, porches, balconies, ladders, stairs, etc.) are also situations where the Code wants to prevent accidental or intentional contact. Contact with these conductors could result in electric shock or electrocution.
It's worth noting that this rule does not apply to the SE cable, itself, but rather only the exposed conductors. If the service conductors were "open" conductors or made up of a cable that does not have an overall jacketing, they would also be subject to the clearance given here. However, the SE cable is permitted to be closer than 3 ft, but the conductors that are uncovered must be at least 3 ft away.
While perhaps not as aesthetically pleasing as the installation shown here, the service cable could have been routed at an angle, away from the window, which would have provided the required clearance. This would have required the insulator (attachment point) to be relocated, but it would have done the job.
Alternatively, the cable could have continued up the side of the building until it was at a point where the exposed conductors were above the window. Either of these two options would have ensured compliance with the requirements of 230.9.
Want to use this article? Click here for options!
© 2012 Penton Media, Inc.
Code Challenge
Code Quiz
Feb 2, 2012 9:02 PM, By Steven Owen
When installing audio distribution cables exposed on the surface of ceilings and sidewalls, the cables shall be supported by which of the following products?
- ...
More Code Quizzes
Code Q&A
Feb 2, 2012 8:58 PM, By Mike Holt
Q. Is it acceptable to use a 14 AWG conductor for the bonding jumper to a receptacle on a 20A branch circuit?
...
More Code Q&As
Acceptable Use Policy blog comments powered by Disqus
advertisement
product spotlight
Labeling tool
Feb 10, 2012 7:58 AM
The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.