What's Wrong Here?
Aug 1, 2010 12:00 PM, By Brian J. McPartland, NEC Consultant
Here’s your chance to moonlight as an electrical inspector and second-guess someone else’s work from the safety of your living room or office. Can you identify the Code violation(s) in this photo?
Hint: “X” marks the spot.
Tell Them What They’ve Won
Using the 2008 NEC, correctly identify the Code violation(s) in this month’s photo — in 200 words or less — and you could win something to put in your toolbox. E-mail your response to electrical.group@penton.com, and we’ll select three winners (excluding manufacturers and prior winners) at random from the correct submissions. Winners will receive a set of insulated hand tools from Ideal Industries, Inc., valued at more than $125. (Please allow six to eight weeks for delivery of tools.)
June Winners
This month’s winners include: John Sokolik, senior project manager, Pelican Engineering Consultants, LLC, Naples, Fla.; Darin Hultberg, electrical engineering technician, Advanced Engineering and Environmental Services, Inc., Grand Forks, N.D.; and Richard Owen, partner, Owen Electrical Contracting, Oakdale, Minn. Although these three responded quickly and accurately, almost all of the submissions that we received this month made reference to the most glaring clearance violations shown in this photo.
As noted in 230.9(A), “Service conductors installed as open conductors or multi-conductor cable without an overall outer jacket shall have a clearance of not less than 900 mm (3 ft) from windows that are designed to be opened, doors, porches, balconies, ladders, stairs, fire escapes, or similar locations.” In addition, 230.9(B) states, “The vertical clearance of final spans above, or within 900 mm (3 ft) measured horizontally of, platforms, projections, or surfaces from which they might be reached shall be maintained in accordance with 230.24(B).” It’s clear the service conductor is within reach of anyone who stands on this open balcony space. Section 230.24 begins with the phrase, “Service-drop conductors shall not be readily accessible.”
The communications cable below the service conductors can also be cited. As noted in 800.44(A)(4), “Supply service drops of 0-750V running above and parallel to communications service drops shall have a minimum separation of 300 mm (12 in.) at any point in the span, including the point of their attachment to the building.” The distance between the power and communications cable near the point of attachment is less than 12 in.
Although it’s difficult to see in this photo, one might also call into question the means of attachment at the building (230.27) and the mounting supports used (230.51) for support of the service-drop conductor.
Want to use this article? Click here for options!
© 2012 Penton Media, Inc.
Code Challenge
Code Quiz
May 10, 2012 12:29 PM, By Steven Owen, National Code Seminars
When installing a shielded cable or a twisted pair cable in a Class I, Division 1 location where a cable seal is required, when is it not required to remove the shielding material or separate the twisted pairs of those type cables?...
More Code Quizzes
Code Q&A
May 24, 2012 10:42 AM, By Mike Holt, NEC Consultant
Q. What labeling does the Code require in regard to arc flash hazard warning?...
More Code Q&As
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
What's Wrong Here?
May 10, 2012 12:44 PM
View all What's Wrong Here?
What's Wrong Here
Sponsored By:
product spotlight
EV charger tester
May 25, 2012 8:26 AM
The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.