What's Wrong Here?
Jun 1, 2010 12:00 PM, By Brian J. McPartland, NEC Consultant
How well do you know the Code? Think you can spot violations the original installer either ignored or couldn't identify? Here's your chance to moonlight as an electrical inspector and second-guess someone else's work from the safety of your living room or office. Can you identify the Code violation(s) in this photo?
Hint: Has anyone seen the clothespins?
‘TELL THEM WHAT THEY'VE WON…’
Using the 2008 NEC, correctly identify the Code violation(s) in this month's photo — in 200 words or less — and you could win something to put in your toolbox. E-mail your response to electrical.group@penton.com, and we'll select three winners (excluding manufacturers and prior winners) at random from the correct submissions. Winners will receive a set of insulated hand tools from Ideal Industries, Inc., valued at more than $125.* The set includes 9.25-in. insulated side-cutting pliers, 10-in. insulated tongue-and-groove pliers, and a 0.25-in. × 6-in. insulated screwdriver. (* Please allow six to eight weeks for delivery of tools.)
April Winners
There were a good number of responses to this particular installation. Surprisingly, however, only a few identified all the violations shown in this photo. This month's winners include: Brian Roessler, electrician, Brian's Electric, Madison, Wis.; and Ed Odell, president, Odell Electric, Stony Point, N.Y.
First, as given in 250.53(G) [Rod and Pipe Electrodes], “The electrode shall be installed such that at least 2.44 m (8 ft) of length is in contact with the soil.” Unless this is a 10-ft rod, which is not the norm, we have a violation.
Second, this same section of the Code also says, “The upper end of the electrode shall be flush with or below grade level unless the above-ground end and the grounding electrode conductor attachment are protected against physical damage as specified in 250.10.” Compliance with the requirement in 250.10 is difficult to obtain, at best. And exactly what must be done is hard to envision. The best approach is to ensure that the rod is “flush with or below grade.”
Third, Sec. 250.53(A) states, “Where practicable rod, pipe, and plate electrodes shall be embedded below the permanent moisture level.” It's hard to know if compliance with this rule is impracticable, but if that is the case, the burden of proof would be on the installer. How one would go about establishing the impracticability of compliance is not exactly clear.
Lastly, the fourth sentence in 250.70 [Methods of Grounding and Bonding Conductor Connection to Electrodes] says, “Not more than one conductor shall be connected to the grounding electrode by a single clamp or fitting unless the clamp or fitting is listed for multiple conductors.”
Want to use this article? Click here for options!
© 2012 Penton Media, Inc.
Code Challenge
Code Quiz
May 10, 2012 12:29 PM, By Steven Owen, National Code Seminars
When installing a shielded cable or a twisted pair cable in a Class I, Division 1 location where a cable seal is required, when is it not required to remove the shielding material or separate the twisted pairs of those type cables?...
More Code Quizzes
Code Q&A
May 24, 2012 10:42 AM, By Mike Holt, NEC Consultant
Q. What labeling does the Code require in regard to arc flash hazard warning?...
More Code Q&As
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
What's Wrong Here?
May 10, 2012 12:44 PM
View all What's Wrong Here?
What's Wrong Here
Sponsored By:
product spotlight
EV charger tester
May 25, 2012 8:26 AM
The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.



































