What's Wrong Here?

May 1, 2009 12:00 PM

Here’s your chance to moonlight as an electrical inspector and second-guess someone else’s work from the safety of your living room or office. Can you identify the Code violation(s) in this photo?

How well do you know the Code? Think you can spot violations the original installer either ignored or couldn’t identify? Here’s your chance to moonlight as an electrical inspector and second-guess someone else’s work from the safety of your living room or office. Can you identify the Code violation(s) in this photo?

Hint: Overexposed and unstable








March Winners

Our three winners this month were: Bob Allsbrook, project manager, Pedro Falcon Electrical Contractors, Inc., Big Pine Key, Fla.; David James, Puckett Electric, Durango, Colo.; and David Martinez, journeyman electrician, JM Electric, Salinas, Calif. This group identified the following violations associated with this unusual pole-mounted meter can.

• Plumbing pipe elbows are not approved for use as an electrical conduit. As per 352.6, “PVC conduit, factory elbows, and associated fittings shall be listed.” Also see 352.2 for the definition of rigid polyvinyl chloride conduit (PVC) and 352.100 for the construction specifications of PVC.

• These plumbing pipe elbows do not meet the radius criteria of Table 2 in Chapter 9. As per 352.24, “The radius of the curve to the centerline of such bends shall not be less than shown in Table 2, Chapter 9.”

• The plumbing pipe fitting at the meter socket enclosure does not meet the requirements of 352.48, which states, “All joints between lengths of conduit, and between conduit and couplings, fittings, and boxes, shall be made by an approved method.” In addition, 312.2 requires meter enclosures installed in wet locations to be installed in such a manner to prevent moisture from entering.

• A review of 352.10 and 352.12 would also be beneficial, as these sections of the Code outline where you can and cannot use PVC conduit.

‘TELL THEM WHAT THEY'VE WON…’

Using the 2008 NEC, correctly identify the Code violation(s) in this month’s photo — in 200 words or less — and you could win something to put in your tool box. E-mail your response to electrical.group@penton.com, and we’ll select three winners (excluding manufacturers and prior winners) at random from the correct submissions. Winners will receive a set of insulated hand tools from Ideal Industries, Inc., valued at more than $125.* The set includes 9.25-in. insulated side-cutting pliers, 10-in. insulated tongueand- groove pliers, and a 0.25-in. x 6-in. insulated screwdriver. (* Please allow six to eight weeks for delivery of tools.)

Want to use this article? Click here for options!

Code Challenge

Code Quiz

May 10, 2012 12:29 PM, By Steven Owen, National Code Seminars

When installing a shielded cable or a twisted pair cable in a Class I, Division 1 location where a cable seal is required, when is it not required to remove the shielding material or separate the twisted pairs of those type cables?...


More Code Quizzes

Code Q&A

May 24, 2012 10:42 AM, By Mike Holt, NEC Consultant

Q. What labeling does the Code require in regard to arc flash hazard warning?...


More Code Q&As
 



Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

May 10, 2012 12:44 PM

What's Wrong Here?

Apr 19, 2012 10:09 AM

What's Wrong Here?

Apr 5, 2012 2:27 PM

View all What's Wrong Here?

product spotlight

EV charger tester

May 25, 2012 8:26 AM

EV charger tester

The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M Whitepaper

Arc Mitigation –A Three-Step Approach

Did you know that an arc-flash incident hospitalizes 5-7 workers per day in North America, severely impacting processes and profitability with lost production? Download This Sponsored Whitepaper Today!

What's New in Residential Cabling?
Date: Wednesday, May 30, 2012
Time: 2:00pm ET


In this The Home Depot sponsored Low Voltage Webinar, Ron Kipper RCDD / NTS will discuss the need for compression style coaxial connectors and the migration of the entire CATV, Satellite and Audio / Video industry to them. Register Today!

Grounding Versus Bonding
Now Available On-Demand


In this 60-minute FREE webinar, Mike Holt of Mike Holt Enterprises, Inc. will explain the purpose of grounding and bonding as related to the most current requirements set forth in the 2011 NEC. Register to View On-Demand!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues