What's Wrong Here?

May 1, 2009 12:00 PM

Here’s your chance to moonlight as an electrical inspector and second-guess someone else’s work from the safety of your living room or office. Can you identify the Code violation(s) in this photo?

How well do you know the Code? Think you can spot violations the original installer either ignored or couldn’t identify? Here’s your chance to moonlight as an electrical inspector and second-guess someone else’s work from the safety of your living room or office. Can you identify the Code violation(s) in this photo?

Hint: Overexposed and unstable








March Winners

Our three winners this month were: Bob Allsbrook, project manager, Pedro Falcon Electrical Contractors, Inc., Big Pine Key, Fla.; David James, Puckett Electric, Durango, Colo.; and David Martinez, journeyman electrician, JM Electric, Salinas, Calif. This group identified the following violations associated with this unusual pole-mounted meter can.

• Plumbing pipe elbows are not approved for use as an electrical conduit. As per 352.6, “PVC conduit, factory elbows, and associated fittings shall be listed.” Also see 352.2 for the definition of rigid polyvinyl chloride conduit (PVC) and 352.100 for the construction specifications of PVC.

• These plumbing pipe elbows do not meet the radius criteria of Table 2 in Chapter 9. As per 352.24, “The radius of the curve to the centerline of such bends shall not be less than shown in Table 2, Chapter 9.”

• The plumbing pipe fitting at the meter socket enclosure does not meet the requirements of 352.48, which states, “All joints between lengths of conduit, and between conduit and couplings, fittings, and boxes, shall be made by an approved method.” In addition, 312.2 requires meter enclosures installed in wet locations to be installed in such a manner to prevent moisture from entering.

• A review of 352.10 and 352.12 would also be beneficial, as these sections of the Code outline where you can and cannot use PVC conduit.

‘TELL THEM WHAT THEY'VE WON…’

Using the 2008 NEC, correctly identify the Code violation(s) in this month’s photo — in 200 words or less — and you could win something to put in your tool box. E-mail your response to electrical.group@penton.com, and we’ll select three winners (excluding manufacturers and prior winners) at random from the correct submissions. Winners will receive a set of insulated hand tools from Ideal Industries, Inc., valued at more than $125.* The set includes 9.25-in. insulated side-cutting pliers, 10-in. insulated tongueand- groove pliers, and a 0.25-in. x 6-in. insulated screwdriver. (* Please allow six to eight weeks for delivery of tools.)

Want to use this article? Click here for options!

Code Challenge

Code Quiz

Mar 11, 2010 12:45 PM, By Steven Owen

When installing outlet boxes for wall-mounted luminaires, when can you use No. 6 screws to secure the luminaire yoke to a plaster ring?...


More Code Quizzes

Code Q&A

Mar 11, 2010 12:48 PM, By Mike Holt

Q. Can a receptacle be used as a splicing device?...


More Code Q&As
 



Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

Whats Wrong Here?

Mar 11, 2010 12:54 PM

What's Wrong Here?

Feb 18, 2010 5:04 PM

What's Wrong Here?

Feb 4, 2010 5:06 PM

View all What's Wrong Here?

product of the week

Panelboard

March 8, 2010

Panelboard

View all 2010 Products of the Week

Shocking Stats

54
More Industry Statistics

Recent Comments

More...




Professionals provide answers to your questions. Become an expert!


EC&M TV

Arlington CED1 Entrance Hoods

The Scoop Series CED Entrance Plates and Hoods are reversible, non-metallic, single and two-gang versions...

Southwire's 2009 Cable Innovation Road Show

Gain years worth of insight with Southwire’s 2009 Cable Innovation Road Show with Grounding Seminar!

George Brown College

Online Tech Training – Electronics, PLC, and Robotics programs at George Brown College.

 

Listen
Sizing Gen-Sets: Facts, Hints, and Good Judgment
Listen

The complexities of today’s commercial or industrial facility, with their equipment environment of linear and nonlinear loads, places a whole new light on sizing engine-generator sets.

Arc Mitigation - A Total System Approach
There’s no question the risk of arc flash hazards is real in the electrical industry. What many don’t always realize is the impact in business interruption from such events typically far outweighs the physical damage to equipment. View this On Demand Webinar!

Implementing an Industrial Ethernet Infrastructure that's Built to Last
This webinar explores the key benefits of implementing a robust complete, end-to-end Industrial Ethernet solution – from cabling and connectivity, to active components and associated hardware. View this On Demand Webinar!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues