What's Wrong Here?
Oct 1, 2006 12:00 PM, By Joe Tedesco, NEC Columnist
Hint: Opening up a can of worms.
Edward P. Nescot, vice president, Western Operations, The Farfield Co., Greensburg, Pa., provided the following thoughts. “Cables are not properly supported, see Articles 300, 320, and 330 for AC and MC support within 12 inches of every box. The electrical nonmetallic tubing (ENT) is not properly supported [see 362.30(A)]. They used an improper fitting at the EMT and ENT conversion point [see 362.6]. The junction box is severely overcrowded [see 314.16(A)(1)] and has no blank cover plate [see 314.25].”
Richard Rubino, senior electrical inspector, City of Los Angeles, Lomita, Calif., offered a more detailed submission. References not overlapping with Nescot's comments include the following:
300.16(A) — requires a box or fitting when there is a change — in this case from EMT to ENT.
358.30 — calls for the EMT to be securely fastened in place within 3 feet of the box.
362.30 — requires the ENT to be securely fastened in place at intervals not to exceed 3 feet and within 3 feet of the termination.
362.10(1) and (2). If the building is more than three stories, this is a violation. And I don't see any thermal barriers.
362.120 — markings not visible on approximately 6 to 8 feet of ENT (may be on the opposite side).
314.23(A) — may be a violation if the box is not securely fastened to the top plate.
314. 28(C) — calls for all junction boxes to be provided with a cover.
320.24 — appears that the bending radius is less than five times the diameter (if this is Type AC “BX” cable) on the run closest to the bottom of the picture.
In addition to noting some of the same sections as the first two winners, John Ball, a health care electrician from Inman, S.C., added these references.
110.12 — the job was not installed in a neat and workman-like manner.
110.3(B) — the connection from EMT to ENT would not be listed or labeled for this purpose.
110.8 — the connection from EMT to ENT would not be recognized as a suitable wiring method.
300.11(A)(1) or (A)(2) — cables shall not be laid on the suspended ceiling.
362.6 — ENT fitting not listed for direct connection to EMT in this installation.
Want to use this article? Click here for options!
© 2012 Penton Media, Inc.
Code Challenge
Code Quiz
May 10, 2012 12:29 PM, By Steven Owen, National Code Seminars
When installing a shielded cable or a twisted pair cable in a Class I, Division 1 location where a cable seal is required, when is it not required to remove the shielding material or separate the twisted pairs of those type cables?...
More Code Quizzes
Code Q&A
May 24, 2012 10:42 AM, By Mike Holt, NEC Consultant
Q. What labeling does the Code require in regard to arc flash hazard warning?...
More Code Q&As
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
What's Wrong Here?
May 10, 2012 12:44 PM
View all What's Wrong Here?
What's Wrong Here
Sponsored By:
product spotlight
EV charger tester
May 25, 2012 8:26 AM
The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.