What's Wrong Here?

Sep 1, 2006 12:00 PM, By Joe Tedesco, NEC Columnist

Hint: This receptacle is located behind a bed in a hotel guestroom.

Candi Brackett, chief engineer, Wilmington Hilton Riverside, Wilmington, Del., offered these comments. “In reference to the receptacle behind the hotel bed, the 1999 NEC [210.60 (B)] was the first edition of the Code to reference this issue. We have had many damaged in the past. The new requirement for the receptacle is that it shall be located so that the bed does not come in contact with the attachment plugs, or a suitable guard must be put in place.”

James W. Robertson, Jr., master electrician, J.E.C. Electric, Inc., Fort Wayne, Ind., added this perspective. “The main violation I see here is under 210.60(B). After adoption of the 1999 NEC, receptacles behind a bed in a hotel room shall be located such that when cords are plugged in that the bed does not make contact with them causing damage. Secondly, a suitable guard could also be installed to prevent damage for any existing receptacles as well.”

Sharon Milholen, electrical design engineer, Patterson Pump Co., Toccoa, Ga., summed it up as follows: “Per 210.60 (B) — Only after the 1999 NEC was adopted, either the bed cannot be able to touch any plug connected to the receptacle, or the receptacle must be provided with a guard. Beats me as to what a ‘suitable guard' is!”

> Try Another Quiz

Want to use this article? Click here for options!

Code Challenge

Code Quiz

Mar 11, 2010 12:45 PM, By Steven Owen

When installing outlet boxes for wall-mounted luminaires, when can you use No. 6 screws to secure the luminaire yoke to a plaster ring?...


More Code Quizzes

Code Q&A

Mar 11, 2010 12:48 PM, By Mike Holt

Q. Can a receptacle be used as a splicing device?...


More Code Q&As
 



Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

Whats Wrong Here?

Mar 11, 2010 12:54 PM

What's Wrong Here?

Feb 18, 2010 5:04 PM

What's Wrong Here?

Feb 4, 2010 5:06 PM

View all What's Wrong Here?

product of the week

CAD Software

March 15, 2010

CAD Software

View all 2010 Products of the Week

Shocking Stats

54
More Industry Statistics

Recent Comments

More...




Professionals provide answers to your questions. Become an expert!


EC&M TV

Arlington CED1 Entrance Hoods

The Scoop Series CED Entrance Plates and Hoods are reversible, non-metallic, single and two-gang versions...

Southwire's 2009 Cable Innovation Road Show

Gain years worth of insight with Southwire’s 2009 Cable Innovation Road Show with Grounding Seminar!

George Brown College

Online Tech Training – Electronics, PLC, and Robotics programs at George Brown College.

 

Listen
Sizing Gen-Sets: Facts, Hints, and Good Judgment
Listen

The complexities of today’s commercial or industrial facility, with their equipment environment of linear and nonlinear loads, places a whole new light on sizing engine-generator sets.

Arc Mitigation - A Total System Approach
There’s no question the risk of arc flash hazards is real in the electrical industry. What many don’t always realize is the impact in business interruption from such events typically far outweighs the physical damage to equipment. View this On Demand Webinar!

Implementing an Industrial Ethernet Infrastructure that's Built to Last
This webinar explores the key benefits of implementing a robust complete, end-to-end Industrial Ethernet solution – from cabling and connectivity, to active components and associated hardware. View this On Demand Webinar!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues