What's Wrong Here?
Aug 1, 2006 12:00 PM, By Joe Tedesco, NEC Columnist
Hint: Locknuts and couplings transition?
Brian Newland, an electrical engineer in Savannah, Ga., noted that the transition from flexible metal conduit to EMT is prohibited by the Code. “A box or conduit body must be in place to make the transition. Per 300.15, ‘Fittings and connectors shall be used only with the specific wiring methods for which they are designed and listed.’ Also per 358.42, ‘Fittings have been tested for use only with steel EMT unless there is specific marking on the device or carton to indicate the fittings are suitable for use with aluminum or other material.’”
Nicholas S. Mintier, an electrician with Alico Road Aggregate Quarry in Fort Myers, Fla., submitted these comments. “When changing from cable to other raceway wiring methods, …‘a fitting identified for the use’… must be used. Reference 300.15(F).” He noted the one in this photo would loosen over time.
Kathleen McGloin, a Code enthusiast from Boston, added this to the mix. “The installer did not use an electrical box or other listed enclosure to transition from one wiring method to the other. The run is transitioning from flexible metal conduit to non-flexible conduit (at best), or, from armored cable to pipe (at worst). I believe the installation violates the requirements of 300.16(A) and 300.10.”
Want to use this article? Click here for options!
© 2012 Penton Media, Inc.
Code Challenge
Code Quiz
May 10, 2012 12:29 PM, By Steven Owen, National Code Seminars
When installing a shielded cable or a twisted pair cable in a Class I, Division 1 location where a cable seal is required, when is it not required to remove the shielding material or separate the twisted pairs of those type cables?...
More Code Quizzes
Code Q&A
May 24, 2012 10:42 AM, By Mike Holt, NEC Consultant
Q. What labeling does the Code require in regard to arc flash hazard warning?...
More Code Q&As
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
What's Wrong Here?
May 10, 2012 12:44 PM
View all What's Wrong Here?
What's Wrong Here
Sponsored By:
product spotlight
EV charger tester
May 25, 2012 8:26 AM
The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.