Mar 1, 2006 12:00 PM, By Joe Tedesco, NEC Columnist

Answer:

Hint: Interesting weep hole design.

Vernon Long, owner, Long Electrical Services LLC, Sandwich, Ill., submitted a list of five pertinent violations. “The conduit body in the photograph has been compromised for the following reasons:

“1. Violation of 110.11 — By placing the conduit body at grade level, it is subject to frequent exposure to water. If this were located in an area where snow or ice melting agents are commonly used, this would be very deleterious to ferrous metals.

“2. Violation of 110.12(C) — The hole in the cover of the conduit body will now allow water or vermin to enter the raceway system. This can cause additional damage to the raceway and equipment within the facility, possibly resulting in a catastrophic electrical fault.

“3. Violation of 300.6 — If it was necessary to install the conduit body at grade, a nonmetallic unit would have been a better choice.

“4. Violation of 314.15(A) — By not paying sufficient attention to the mounting environment of the conduit body, moisture is now entering and/or accumulating within the unit — and undoubtedly flowing further into the raceway system.

“5. Violation of 300.7 — If this installation is located in a northern climate, the corrosion could also have occurred from within the conduit body, due to the accumulation of condensation. Sealing the raceway at the interior side of the wall would have eliminated this problem.”

Jayson Ouillette, of Ashcott Electrical in Manchester, Mich., injected a little humor in his reply. “This photo suggests that the term LB might in fact be an acronym for ‘Leaky Back.’ There are several noticeable violations in this installation: reference 2005 NEC, Sections 314.15(A), 314.28(C), 314.72(C), and possibly (A) and (E). We might also consider 314.40(A) or 314.41. Perhaps the bottle to the right indicates the motive for leaving this installation as is.”

Glenn Ross, senior electrical designer, Burns and McDonnell, Kansas City, Mo., added that this installation violates the requirements of 110.27, especially section B, and 314.15(A). “If the cover wasn't damaged, it was corroded, and not corrosion resistant as specified in 314.40(A).”

> Try Another Quiz

Want to use this article? Click here for options!

Code Challenge

Code Quiz

Feb 2, 2012 9:02 PM, By Steven Owen

When installing audio distribution cables exposed on the surface of ceilings and sidewalls, the cables shall be supported by which of the following products?

    ...


More Code Quizzes

Code Q&A

Feb 2, 2012 8:58 PM, By Mike Holt

Q. Is it acceptable to use a 14 AWG conductor for the bonding jumper to a receptacle on a 20A branch circuit?

...


More Code Q&As
 



Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

Feb 2, 2012 7:54 PM

What's Wrong Here?

Jan 19, 2012 4:06 PM

What's Wrong Here?

Jan 5, 2012 11:53 AM

View all What's Wrong Here?

product spotlight

Labeling tool

Feb 10, 2012 7:58 AM

Labeling tool

The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M TV

Arlington CP9000

Arlington's new 9" diameter ceiling cover plate is the neatest way to cover unused "high hat" cans. With no tools needed, installation couldn't be faster!...

Arlington Gangable Boxes

Designed for new or retrofit applications, these snap-together gangable plastic boxes eliminate the need to construct a multiple-gang steel box out of several individual ones...

Understanding NEC Requirements for Solar Photovoltaic Systems
During this session, Mike Holt will address possible conflicts or confusing NEC requirements, provide tips on proper electrical installation techniques, and discuss the dangers related to improper installations. View this On Demand Webinar!



resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues