Mar 1, 2006 12:00 PM, By Joe Tedesco, NEC Columnist
Answer:
Hint: Interesting weep hole design.
Vernon Long, owner, Long Electrical Services LLC, Sandwich, Ill., submitted a list of five pertinent violations. “The conduit body in the photograph has been compromised for the following reasons:
“1. Violation of 110.11 — By placing the conduit body at grade level, it is subject to frequent exposure to water. If this were located in an area where snow or ice melting agents are commonly used, this would be very deleterious to ferrous metals.
“2. Violation of 110.12(C) — The hole in the cover of the conduit body will now allow water or vermin to enter the raceway system. This can cause additional damage to the raceway and equipment within the facility, possibly resulting in a catastrophic electrical fault.
“3. Violation of 300.6 — If it was necessary to install the conduit body at grade, a nonmetallic unit would have been a better choice.
“4. Violation of 314.15(A) — By not paying sufficient attention to the mounting environment of the conduit body, moisture is now entering and/or accumulating within the unit — and undoubtedly flowing further into the raceway system.
“5. Violation of 300.7 — If this installation is located in a northern climate, the corrosion could also have occurred from within the conduit body, due to the accumulation of condensation. Sealing the raceway at the interior side of the wall would have eliminated this problem.”
Jayson Ouillette, of Ashcott Electrical in Manchester, Mich., injected a little humor in his reply. “This photo suggests that the term LB might in fact be an acronym for ‘Leaky Back.’ There are several noticeable violations in this installation: reference 2005 NEC, Sections 314.15(A), 314.28(C), 314.72(C), and possibly (A) and (E). We might also consider 314.40(A) or 314.41. Perhaps the bottle to the right indicates the motive for leaving this installation as is.”
Glenn Ross, senior electrical designer, Burns and McDonnell, Kansas City, Mo., added that this installation violates the requirements of 110.27, especially section B, and 314.15(A). “If the cover wasn't damaged, it was corroded, and not corrosion resistant as specified in 314.40(A).”
Want to use this article? Click here for options!
© 2012 Penton Media, Inc.
Code Challenge
Code Quiz
May 10, 2012 12:29 PM, By Steven Owen, National Code Seminars
When installing a shielded cable or a twisted pair cable in a Class I, Division 1 location where a cable seal is required, when is it not required to remove the shielding material or separate the twisted pairs of those type cables?...
More Code Quizzes
Code Q&A
May 24, 2012 10:42 AM, By Mike Holt, NEC Consultant
Q. What labeling does the Code require in regard to arc flash hazard warning?...
More Code Q&As
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
What's Wrong Here?
May 10, 2012 12:44 PM
View all What's Wrong Here?
What's Wrong Here
Sponsored By:
product spotlight
EV charger tester
May 25, 2012 8:26 AM
The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.