What's Wrong Here?
Nov 1, 2005 12:00 PM, By Joe Tedesco, NEC Columnist
Answer:
Hint: Yes, the cover is missing, but can you identify this piece of equipment and tell what else is wrong with the installation?
This is a main disconnect switch for a building I ran across in the Boston area. Many of these are still in use in this part of the country. Although the Code isn't retroactive, the following references could be cited if this installation was inspected in accordance with the latest edition of the NEC.
Tony Scaffidi, technical support engineer, Pieper Electric, Milwaukee, sent in these comments. “This is a fused disconnect. The small lever in the middle of the enclosure engages the fuses and either opens or closes the switch when turned. It looks like the grounded conductor is being tapped, which is a direct violation of 404.3(B). If this was a service disconnect, you would be disconnecting the neutral and service grounding.”
Albert Howitt, electrician, Bonte Electrical, Houston, had this to say. “The enclosure raceway is missing an insulated fitting. This would be required if we were to reference the current edition of the Code, as per 300.4(F). The tap conductor connection could also be a violation of 110.14(A), and the installation might also violate the tap conductor requirements of 240.21 (A) through (G).”
Mike Svasta, electrical designer, Peters, Tschantz & Bandwen, Inc., Akron, Ohio, added this to the mix. “The equipment, with its missing cover, could possibly lead to a shock hazard, since it's located so close to the public street. One way to overcome this hazard would be to replace the main switch shown here with a new one located in the basement of the building.
Want to use this article? Click here for options!
© 2012 Penton Media, Inc.
Code Challenge
Code Quiz
May 10, 2012 12:29 PM, By Steven Owen, National Code Seminars
When installing a shielded cable or a twisted pair cable in a Class I, Division 1 location where a cable seal is required, when is it not required to remove the shielding material or separate the twisted pairs of those type cables?...
More Code Quizzes
Code Q&A
May 24, 2012 10:42 AM, By Mike Holt, NEC Consultant
Q. What labeling does the Code require in regard to arc flash hazard warning?...
More Code Q&As
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
What's Wrong Here?
May 10, 2012 12:44 PM
View all What's Wrong Here?
What's Wrong Here
Sponsored By:
product spotlight
EV charger tester
May 25, 2012 8:26 AM
The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.