What's Wrong Here?
Sep 1, 2005 12:00 PM, By Joe Tedesco, NEC Columnist
Answer:
Hint: Is there a more dangerous violation out there?
This gasoline dispenser is located adjacent to an active job site. To top it off, the tank sits directly behind a city hall in West Virginia — where it's used to fuel city-owned vehicles, including the one driven by the AHJ and his assistant.
Congratulations to the following three readers, who correctly identified the problems associated with this installation: Dan Naugle, P.E., engineering manager, Boeing Corp., Moore, Okla.; Nick Volpenhein, E.I.T., project manager, Volpenhein Brothers Electric, Cincinnati; and Kyle Aylor, project manager, Valentine Electrical, Ashland, Va.
It appears this installation might have been compliant at some point (i.e., rigid conduit, seal-off, explosionproof devices, etc.), but what's here now certainly doesn't comply with the requirements of Art. 501 for a Class I, Division 1 location.
The box is not properly supported, and there should be a seal-off between the tee and switch box. There doesn't appear to be an equipment-grounding conductor running to the pump motor, and getting to the switch to turn on the pump or perform maintenance may yield accessibility issues. Let's not forget about those open-air connections in a hazardous (classified) location!
The missing seal doesn't prevent moisture from entering or accumulating within the box, conduit body, or fitting. This is a violation of 314.15(A). You can also cite this installation as not meeting the requirements of 501.15(E)(1).
The requirements of Art. 514 for motor fuel dispensing facilities also apply to this installation. However, the current equipment configuration would never comply with Table 514.3(B)(1).
Want to use this article? Click here for options!
© 2012 Penton Media, Inc.
Code Challenge
Code Quiz
May 10, 2012 12:29 PM, By Steven Owen, National Code Seminars
When installing a shielded cable or a twisted pair cable in a Class I, Division 1 location where a cable seal is required, when is it not required to remove the shielding material or separate the twisted pairs of those type cables?...
More Code Quizzes
Code Q&A
May 24, 2012 10:42 AM, By Mike Holt, NEC Consultant
Q. What labeling does the Code require in regard to arc flash hazard warning?...
More Code Q&As
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
What's Wrong Here?
May 10, 2012 12:44 PM
View all What's Wrong Here?
What's Wrong Here
Sponsored By:
product spotlight
EV charger tester
May 25, 2012 8:26 AM
The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.