What's Wrong Here?
Jun 1, 2005 12:00 PM, By Joe Tedesco, NEC Columnist
Answer:
Hint: Is this cleaning equipment being stored in an electrical room or is this electrical equipment being stored in a cleaning supply storage area?
Larry Castillo, electric shop foreman, Denver Water Department, Denver; Dennis Schlitt, senior electrical engineer, Integrated Design Solution, Troy, Mich.; and George Farrell, proprietor, George W. Farrell & Associates, Crystal Lake, Ill., identified quite a few Code violations, poor design and installation practices, and breaches of safety in the June photo:
-
Lack of working clearance in front of panelboards and transformer [110.26(A)].
-
Lack of adequate ventilation around transformer (450.45).
-
The conduit above the blue cabinet isn't adequately supported within 3 feet of the cabinet [344.30(A)].
-
The copper water line above the panelboards violates the dedicated space requirement of 110.26(F)(1)(a).
-
There appears to be corrugated cardboard (maybe carpeting strips) stacked against the switchboard to left. And a roll of what appears to be carpet is stacked between the blue wall-mounted panelboard and the green object, which appears to be a ventilated transformer. And ladders and other objects are leaning against the side of the enclosed circuit breaker on the back wall. This violates 110.23(A) and (B) and possibly 450.9.
-
Access is blocked by carts and other materials. This doesn't meet requirements for readily accessible or for working space. [Definitions and 110.26 (A) and (B) and 450.13].
-
Possible hazardous and/or flammable materials in the form of cleaning supplies are stored in this space. The vapors from these supplies often attack insulation or corrode metals [110.11, FPN No. 2].
-
Large blue tank in foreground appears to contain pressurized substances.
-
Although this is a recent NEC addition and isn't retroactive, safety would be improved if the equipment had arc-flash hazard labels installed in accordance with 110.16 of 2005 NEC.
Want to use this article? Click here for options!
© 2012 Penton Media, Inc.
Code Challenge
Code Quiz
Feb 2, 2012 9:02 PM, By Steven Owen
When installing audio distribution cables exposed on the surface of ceilings and sidewalls, the cables shall be supported by which of the following products?
- ...
More Code Quizzes
Code Q&A
Feb 2, 2012 8:58 PM, By Mike Holt
Q. Is it acceptable to use a 14 AWG conductor for the bonding jumper to a receptacle on a 20A branch circuit?
...
More Code Q&As
Acceptable Use Policy blog comments powered by Disqus
advertisement
product spotlight
Labeling tool
Feb 10, 2012 7:58 AM
The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.