ECM Buyers' Guide

What's Wrong Here?

Nov 1, 2004 12:00 PM, By Joe Tedesco, NEC Columnist

How well do you know the Code?

Hint: Support isn't required for these metallic cables at the point of entry into this framing member.

Thomas Sessa, electrical engineer, U.S. Army COE, New York City, submitted these comments in reference to the photo in the November issue. “The AC cables shall be secured by staples, cable ties, straps, hangers, or similar fittings designed and installed so as not to damage the cable at intervals not exceeding 4½ feet and within 12 inches of outlet boxes, junction boxes, cabinets, or fittings (Art. 322.30),” he wrote. “Unsupported cables are allowed only if installed as noted in Art. 320.30(B), 1 through 3. In addition, armored cable installed in other than vertical runs through bored or punched holes in wood or metal framing members, or through notches in wooden framing members may require protection by steel plates at least 1/16 inch thick.”

Paul Blecharczyk, P.E., principal applications engineer, Invensys Foxboro, East Bridgewater, Mass., submitted these comments. “I found that the three BX cables in bored holes appear to be in danger of physical damage,” he wrote. “With regard to 300.4(A)(1), the Code specifies, ‘In both exposed and concealed locations, where a cable or raceway-type wiring method is installed through bored holes in joists, rafters, or wood members, holes shall be bored so that the edge of the hole is not less than 1¼ inches from the nearest edge of the wood member. Where this distance can't be maintained, the cable or raceway shall be protected from penetration by screws or nails by a steel plate or bushing, at least 1/16 inch thick, and of appropriate length and width installed to cover the area of the wiring.’ This does not appear to be the case in this photo.”

Dan Naugle, P.E., engineering manager, Boeing, Moore, Okla., also cited violations of 300.4.

Want to use this article? Click here for options!

product of the week

Thermal imaging software

November 17, 2008 10:26 AM

Fluke SmartView Version 2.0

View all 2008 Products of the Week

Recent Comments

Follow comments on ecmweb.com




Arc Flash Conferences   Code Change Conferences

Professionals provide answers to your questions.



Do you have any technical paper explaining IBC?

iGard Resistance Grounding Q&A BookletDownload the Resistance Grounding Q&A Booklet
I-Gard
EC&M TV

Arlington Indoor InBox

Easy install makes Indoor InBox preferred for power & low voltage applications. Furniture and appliances stay close to the wall!...

Listen
"Sizing Gen-Sets: Facts, Hints, and Good Judgment"
Listen
Sponsored By:

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Back to Top

Browse Back Issues

Browse Back Issues