What's Wrong Here?
Oct 1, 2004 12:00 PM, By Joe Tedesco, NEC Columnist
How well do you know the Code? Think you can spot violations the original installer either ignored or couldn't identify? Here's your chance to moonlight as an electrical inspector and second-guess someone else's work from the safety of your living room or office. Joe Tedesco, who has a knack for finding shoddy electrical work, did the dirty work and found this mess. Now it's your turn to identify the violation.
Hint: Would you like to fill up your vehicle with fuel near this installation?
We would need a lot more space than allotted on this page to fully list all of the problems shown at this motor fuel dispensing facility. The following is a list of a few of the most important violations of the 2002 NEC identified by this month's winners — Ray Clarke, P.E., senior project engineer, Pipeline System, Inc., Concord, Calif., and Joey Ray, electrical apprentice, Hayes & Lunsford of Asheville, N.C., Horse Shoe, N.C.
All electrical equipment and wiring installed in a Class I location as classified in 514.3 shall comply with the applicable provisions of Art. 501.
A listed seal is required to be provided in each conduit run that enters or leaves a dispenser or any cavities or enclosures in direct communication therewith. The sealing fitting must be the first fitting after the conduit emerges from the earth or concrete. See 514.9(A) for sealing at dispensers and 514.9(B) for sealing rules at boundaries. A threaded RMC coupling isn't an acceptable first fitting. Many installers misinterpret this rule.
In addition to the grounding rules of Art. 250, this installation must also meet the requirements of 501.16 and 514.16.
The gutter in this installation also violates the substantial construction requirements of 366.10(B) and the securing and supporting requirements for rigid conduit in 344.30 aren't met.
Want to use this article? Click here for options!
© 2012 Penton Media, Inc.
Code Challenge
Code Quiz
Feb 2, 2012 9:02 PM, By Steven Owen
When installing audio distribution cables exposed on the surface of ceilings and sidewalls, the cables shall be supported by which of the following products?
- ...
More Code Quizzes
Code Q&A
Feb 2, 2012 8:58 PM, By Mike Holt
Q. Is it acceptable to use a 14 AWG conductor for the bonding jumper to a receptacle on a 20A branch circuit?
...
More Code Q&As
Acceptable Use Policy blog comments powered by Disqus
advertisement
product spotlight
Labeling tool
Feb 10, 2012 7:58 AM
The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.