What's Wrong Here?

Mar 1, 2004 12:00 PM, By Joe Tedesco, NEC Columnist

How well do you know the Code?

Hint: Looks like someone's been doing a little troubleshooting work on this fire alarm system.

Scott Stuart, a student at Triangle Tech in DuBois, Pa., generated this lengthy list of references to point out the violations noted in this photo:

  • 110.12(A) — unused knockouts in the metal box must be closed

  • 110.14(A) — eliminate exposed bare wires

  • 314.28(C) — all boxes must have approved covers

  • 314.16 and 314.16(A) — box fill calculation clearly not followed

  • 760.10 — circuit identification is missing

  • 760.30(A)(1) — place exposed or fished wires in a concealed space

Bill Gallus, an electrician with Habitat for Humanity, Johnstown, Pa., referred to this installation as a “rat's nest” and noted several violations. “Single conductors must be installed as part of an approved wiring method (conduit and box), and conductors of the same circuit must be contained within the same raceway (conduit) [300.3(A) and (B)],” he wrote. “A box or conduit body is required at each conductor splice point (meaning the splice belongs inside the box or conduit body) (300.15). Junction boxes and conduit bodies must have covers [314.28(C)]. The metal box must be grounded (250.110). Workmanship is very bad and questionable (110.12 and 760.6).”

Mike Groff, instructor/electrical designer, GG&S Merchant Systems, Allentown, Pa., added, “Looks like someone was troubleshooting this system and got lost!” He correctly identified the missing wire connectors and noted, “Exposed free ends of wires are required to be spliced or joined with splicing devices identified for the use or covered with an insulation equivalent to the conductors [110.14(B)].”

Want to use this article? Click here for options!

Code Challenge

Code Quiz

Nov 5, 2009 5:24 PM, By Steven Owen

What are the minimum and maximum lengths permitted for the grounding conductor on network-powered broadband communications systems network interface units that contain protectors?...


More Code Quizzes

Code Q&A

Nov 5, 2009 5:30 PM, By Mike Holt

When are tamper-resistant receptacles required?...


More Code Q&As
 


Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

Nov 5, 2009 11:50 AM

What's Wrong Here?

Oct 22, 2009 11:16 PM

What's Wrong Here?

Oct 8, 2009 3:32 PM

View all What's Wrong Here?

product of the week

Video camera scopes

November 16, 2009

Video camera scopes

View all 2009 Products of the Week

Recent Comments

More...


EC&M TV

Exterior Fixture Box for Brick or Stone

Installing a fixture box in a brick or stone wall just got easier with Arlington’s new adjustable depth box!

Southwire's 2009 Cable Innovation Road Show

Gain years worth of insight in only 2-1/2 hours with Southwire’s 2009 Cable Innovation Road Show with Grounding Seminar. The agenda is packed with valuable information that focuses on installation tips!

Listen
Sizing Gen-Sets: Facts, Hints, and Good Judgment
Listen

The complexities of today’s commercial or industrial facility, with their equipment environment of linear and nonlinear loads, places a whole new light on sizing engine-generator sets.

Arc Mitigation - A Total System Approach
There’s no question the risk of arc flash hazards is real in the electrical industry. What many don’t always realize is the impact in business interruption from such events typically far outweighs the physical damage to equipment. View this On Demand Webinar!

Implementing an Industrial Ethernet Infrastructure that's Built to Last
This webinar explores the key benefits of implementing a robust complete, end-to-end Industrial Ethernet solution – from cabling and connectivity, to active components and associated hardware. View this On Demand Webinar!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues