What's Wrong Here?
Mar 1, 2004 12:00 PM, By Joe Tedesco, NEC Columnist
How well do you know the Code?
Hint: Looks like someone's been doing a little troubleshooting work on this fire alarm system.
Scott Stuart, a student at Triangle Tech in DuBois, Pa., generated this lengthy list of references to point out the violations noted in this photo:
110.12(A) — unused knockouts in the metal box must be closed
110.14(A) — eliminate exposed bare wires
314.28(C) — all boxes must have approved covers
314.16 and 314.16(A) — box fill calculation clearly not followed
760.10 — circuit identification is missing
760.30(A)(1) — place exposed or fished wires in a concealed space
Bill Gallus, an electrician with Habitat for Humanity, Johnstown, Pa., referred to this installation as a “rat's nest” and noted several violations. “Single conductors must be installed as part of an approved wiring method (conduit and box), and conductors of the same circuit must be contained within the same raceway (conduit) [300.3(A) and (B)],” he wrote. “A box or conduit body is required at each conductor splice point (meaning the splice belongs inside the box or conduit body) (300.15). Junction boxes and conduit bodies must have covers [314.28(C)]. The metal box must be grounded (250.110). Workmanship is very bad and questionable (110.12 and 760.6).”
Mike Groff, instructor/electrical designer, GG&S Merchant Systems, Allentown, Pa., added, “Looks like someone was troubleshooting this system and got lost!” He correctly identified the missing wire connectors and noted, “Exposed free ends of wires are required to be spliced or joined with splicing devices identified for the use or covered with an insulation equivalent to the conductors [110.14(B)].”
Want to use this article? Click here for options!
© 2012 Penton Media, Inc.
Code Challenge
Code Quiz
Feb 2, 2012 9:02 PM, By Steven Owen
When installing audio distribution cables exposed on the surface of ceilings and sidewalls, the cables shall be supported by which of the following products?
- ...
More Code Quizzes
Code Q&A
Feb 2, 2012 8:58 PM, By Mike Holt
Q. Is it acceptable to use a 14 AWG conductor for the bonding jumper to a receptacle on a 20A branch circuit?
...
More Code Q&As
Acceptable Use Policy blog comments powered by Disqus
advertisement
product spotlight
Labeling tool
Feb 10, 2012 7:58 AM
The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.