ECM Buyers' Guide
    (0)    Follow WWH?

What's Wrong Here?

Feb 1, 2004 12:00 PM, By Joe Tedesco, NEC Columnist

How well do you know the Code? Think you can spot violations the original installer either ignored or couldn't identify? Here's your chance to moonlight as an electrical inspector and second-guess someone else's work from the safety of your living room or office. Joe Tedesco, who has a knack for finding shoddy electrical work, did the dirty work and found this mess. Now it's your turn to identify the violation.

Hint: These flexible cords are “temporarily” being used outside on a concrete crushing site to supply various pieces of electrical equipment.

Mike Barnish, senior electrical designer, Shaw Infrastructure, Inc., Aiken, S.C., questions the temporary nature of this installation. “Temporary? I'll bet that the flexible cord wiring is probably still there as a substitute for the permanent wiring,” Barnish wrote. He goes on to say that not only are the cords not protected from physical damage, but that this installation doesn't even come close to meeting the requirements of 400.8. “Some will argue that it is OK to use cords for the connection of utilization equipment to facilitate frequent interchange. Sorry, but flexible cords and cables simply cannot be used as a substitute for the fixed wiring of a structure, or for this purpose.”

Bradley Nichols, electrical designer, Stearns and Wheler Engineers, Cazenovia, N.Y., added, “If it was true that the cords were used for this temporary installation, then they must be protected from any accidental damage. In this case these cords are likely to be damaged and violate 527.4(H), which states, ‘Flexible cords and cables shall be protected from accidental damage. Sharp corners and projections shall be avoided. Where passing through doorways or other pinch points, protection shall be provided to avoid damage.’”

Shajan Jacob, CEM, senior analyst, NUS Consulting Group, Park Ridge, N.J., also noted that if this job were properly designed, the various circuits would have to be properly protected and would have to originate in an approved distribution center. “I'm afraid that this situation is not easy to rectify, so it may have been allowed on this type of property being away from the public. But where do we draw the line?”

Want to use this article? Click here for options!

Code Challenge

Code Quiz

Nov 5, 2009 5:24 PM, By Steven Owen

What are the minimum and maximum lengths permitted for the grounding conductor on network-powered broadband communications systems network interface units that contain protectors?...


More Code Quizzes

Code Q&A

Nov 5, 2009 5:30 PM, By Mike Holt

When are tamper-resistant receptacles required?...


More Code Q&As
 


Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

Nov 5, 2009 11:50 AM

What's Wrong Here?

Oct 22, 2009 11:16 PM

What's Wrong Here?

Oct 8, 2009 3:32 PM

View all What's Wrong Here?

product of the week

Video camera scopes

November 16, 2009

Video camera scopes

View all 2009 Products of the Week

Recent Comments

More...


EC&M TV

Exterior Fixture Box for Brick or Stone

Installing a fixture box in a brick or stone wall just got easier with Arlington’s new adjustable depth box!

Southwire's 2009 Cable Innovation Road Show

Gain years worth of insight in only 2-1/2 hours with Southwire’s 2009 Cable Innovation Road Show with Grounding Seminar. The agenda is packed with valuable information that focuses on installation tips!

Listen
Sizing Gen-Sets: Facts, Hints, and Good Judgment
Listen

The complexities of today’s commercial or industrial facility, with their equipment environment of linear and nonlinear loads, places a whole new light on sizing engine-generator sets.

Arc Mitigation - A Total System Approach
There’s no question the risk of arc flash hazards is real in the electrical industry. What many don’t always realize is the impact in business interruption from such events typically far outweighs the physical damage to equipment. View this On Demand Webinar!

Implementing an Industrial Ethernet Infrastructure that's Built to Last
This webinar explores the key benefits of implementing a robust complete, end-to-end Industrial Ethernet solution – from cabling and connectivity, to active components and associated hardware. View this On Demand Webinar!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues