Feb 1, 2004 12:00 PM, By Joe Tedesco, NEC Columnist

How well do you know the Code? Think you can spot violations the original installer either ignored or couldn't identify? Here's your chance to moonlight as an electrical inspector and second-guess someone else's work from the safety of your living room or office. Joe Tedesco, who has a knack for finding shoddy electrical work, did the dirty work and found this mess. Now it's your turn to identify the violation.

Hint: These flexible cords are “temporarily” being used outside on a concrete crushing site to supply various pieces of electrical equipment.

Mike Barnish, senior electrical designer, Shaw Infrastructure, Inc., Aiken, S.C., questions the temporary nature of this installation. “Temporary? I'll bet that the flexible cord wiring is probably still there as a substitute for the permanent wiring,” Barnish wrote. He goes on to say that not only are the cords not protected from physical damage, but that this installation doesn't even come close to meeting the requirements of 400.8. “Some will argue that it is OK to use cords for the connection of utilization equipment to facilitate frequent interchange. Sorry, but flexible cords and cables simply cannot be used as a substitute for the fixed wiring of a structure, or for this purpose.”

Bradley Nichols, electrical designer, Stearns and Wheler Engineers, Cazenovia, N.Y., added, “If it was true that the cords were used for this temporary installation, then they must be protected from any accidental damage. In this case these cords are likely to be damaged and violate 527.4(H), which states, ‘Flexible cords and cables shall be protected from accidental damage. Sharp corners and projections shall be avoided. Where passing through doorways or other pinch points, protection shall be provided to avoid damage.’”

Shajan Jacob, CEM, senior analyst, NUS Consulting Group, Park Ridge, N.J., also noted that if this job were properly designed, the various circuits would have to be properly protected and would have to originate in an approved distribution center. “I'm afraid that this situation is not easy to rectify, so it may have been allowed on this type of property being away from the public. But where do we draw the line?”

Want to use this article? Click here for options!

Code Challenge

Code Quiz

Feb 2, 2012 9:02 PM, By Steven Owen

When installing audio distribution cables exposed on the surface of ceilings and sidewalls, the cables shall be supported by which of the following products?

    ...


More Code Quizzes

Code Q&A

Feb 2, 2012 8:58 PM, By Mike Holt

Q. Is it acceptable to use a 14 AWG conductor for the bonding jumper to a receptacle on a 20A branch circuit?

...


More Code Q&As
 



Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

Feb 2, 2012 7:54 PM

What's Wrong Here?

Jan 19, 2012 4:06 PM

What's Wrong Here?

Jan 5, 2012 11:53 AM

View all What's Wrong Here?

product spotlight

Labeling tool

Feb 10, 2012 7:58 AM

Labeling tool

The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M TV

Arlington CP9000

Arlington's new 9" diameter ceiling cover plate is the neatest way to cover unused "high hat" cans. With no tools needed, installation couldn't be faster!...

Arlington Gangable Boxes

Designed for new or retrofit applications, these snap-together gangable plastic boxes eliminate the need to construct a multiple-gang steel box out of several individual ones...

Understanding NEC Requirements for Solar Photovoltaic Systems
During this session, Mike Holt will address possible conflicts or confusing NEC requirements, provide tips on proper electrical installation techniques, and discuss the dangers related to improper installations. View this On Demand Webinar!



resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues