What's Wrong Here?
Nov 1, 2003 12:00 PM, By Joe Tedesco, NEC Columnist
Hint: Is this an approved underground installation?
Joel Nash, design engineer, Tetra Tech, Inc., Pasadena, Calif.; Alan Hartley, Church & Murdock Electric, Erie, Penn.; and Roel Trevino, Trevino Electric, Falfurrias, Texas, all correctly identified the Code violation in the November 2003 column.
After the landscaping work is complete, this sealing fitting won't be accessible for inspection. In addition, this fitting isn't designed for use in direct burial applications.
Per 501.5(C)(1) of the 2002 NEC, “Enclosures for connections or equipment shall be provided with an integral means for sealing, or sealing fittings listed for the location shall be used. Sealing fittings shall be listed for use with one or more specific compounds and shall be accessible.”
Want to use this article? Click here for options!
© 2012 Penton Media, Inc.
Code Challenge
Code Quiz
Feb 2, 2012 9:02 PM, By Steven Owen
When installing audio distribution cables exposed on the surface of ceilings and sidewalls, the cables shall be supported by which of the following products?
- ...
More Code Quizzes
Code Q&A
Feb 2, 2012 8:58 PM, By Mike Holt
Q. Is it acceptable to use a 14 AWG conductor for the bonding jumper to a receptacle on a 20A branch circuit?
...
More Code Q&As
Acceptable Use Policy blog comments powered by Disqus
advertisement
product spotlight
Labeling tool
Feb 10, 2012 7:58 AM
The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.