What's Wrong Here?
Aug 1, 2003 12:00 PM, By Joe Tedesco, NEC Columnist
How well do you know the Code? Think you can spot violations the original installer either ignored or couldn't identify? Here's your chance to moonlight as an electrical inspector and second-guess someone else's work from the safety of your living room or office. Joe Tedesco, who has a knack for finding shoddy electrical work, did the dirty work and found this mess. Now it's your turn to identify the violation.
Hint: This extension cord (upper left) is used in the summer for a fan to keep this building cool.
The following individuals correctly identified the Code violations shown in the August column: Leon Sokhis, electrical engineer, Solar Turbines, Inc., San Diego; Richard Sullivan, junior engineer, Kinsman & Associates, Richardson, Texas; and John Reichardt, electrical designer, Vanderweil Engineers, Alexandria, Va. This extension cord can't be used in any Class I, Division 1 or 2 hazardous (classified) location. Although 501.4(D)(2) permits flexible connections at motor terminals, only flexible explosionproof type fittings that are listed for Class I, Division 1 hazardous (classified) locations, or flexible cord in accordance with the provisions of 501.11 are permitted. These rules don't cover extension cords. See the definition for “Explosionproof Apparatus” in Art. 100 and 500.2 for specific guidance related to electrical equipment installed in hazardous locations.
The installation also violates the requirements of 501.13, which states, “Where condensed vapors or liquids may collect on, or come in contact with, the insulation on conductors, such insulation shall be of a type identified for use under such conditions; or the insulation shall be protected by a sheath of lead or by other approved means.”
Want to use this article? Click here for options!
© 2012 Penton Media, Inc.
Code Challenge
Code Quiz
Feb 2, 2012 9:02 PM, By Steven Owen
When installing audio distribution cables exposed on the surface of ceilings and sidewalls, the cables shall be supported by which of the following products?
- ...
More Code Quizzes
Code Q&A
Feb 2, 2012 8:58 PM, By Mike Holt
Q. Is it acceptable to use a 14 AWG conductor for the bonding jumper to a receptacle on a 20A branch circuit?
...
More Code Q&As
Acceptable Use Policy blog comments powered by Disqus
advertisement
product spotlight
Labeling tool
Feb 10, 2012 7:58 AM
The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.