What's Wronge Here?
The short length of unlisted flexible metal conduit that serves this garage door opener was installed without an equipment-grounding conductor.
Per 250.118 of the 2002 NEC, “The equipment grounding conductor run with or enclosing the circuit conductors shall be one or more or a combination of the following:
“(6) Listed flexible metal conduit that is not listed for grounding, meeting all the following conditions:
“a. The conduit is terminated in fittings listed for grounding.
“b. The circuit conductors contained in the conduit are protected by overcurrent devices rated at 20A or less.
“c. The combined length of flexible metal conduit and flexible metallic tubing and liquidtight flexible metal conduit in the same ground return path does not exceed 1.8 meters (6 feet).
“d. The conduit is not installed for flexibility.”
Want to use this article? Click here for options!
© 2012 Penton Business Media, Inc.
Latest Articles
Emergency lighting controls
Feb 9, 2012 8:40 AM
Cupertino Electric Sponsors Construction Industry Academic Competition
Feb 8, 2012 4:14 PM
John Holland Appointed President of the International Copper Association
Feb 8, 2012 3:53 PM
Trending Articles
Acceptable Use Policy blog comments powered by Disqus
advertisement
product spotlight
Emergency lighting controls
Feb 9, 2012 8:40 AM
The UL924 emergency lighting control relay (ERC) mounts in the ceiling and features an automatic diagnostic feature ...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.