What's Wrong Here?
Answer:
Hint: Cords and cables shall not be used as a substitute
Edwin R. Rosario, P.E., Caribbean Technical Services, Inc., took these pictures in a South Florida commercial building during one of the company’s recent inspection trips. His team went to the building to inspect the CATV and telephone system. However, they found a bunch of Code violations and non-compliance with original drawings and contract documents. What really amazed him was this work had been accepted by local building officials. In fact, it passed final inspection as shown!
As noted in 400.8 of the 2005 NEC, unless specifically permitted in 400.7, flexible cords and cables shall not be used as a substitute for the fixed wiring of a structure or where subject to physical damage.
As noted in the second photo, there are also a lot of blank open positions in this panelboard. Section 408.7 requires the unused openings for circuit breakers and switches to be closed with an identified closure, or other approved means that provides protection substantially equivalent to the wall of the enclosure.
Want to use this article? Click here for options!
© 2012 Penton Business Media, Inc.
Latest Articles
EV charger tester
May 25, 2012 8:26 AM
CFL/LED dimmer
May 24, 2012 8:48 AM
Load bank
May 23, 2012 9:33 AM
Trending Articles
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
What's Wrong Here?
May 10, 2012 12:44 PM
View all What's Wrong Here?
What's Wrong Here
Sponsored By:
product spotlight
EV charger tester
May 25, 2012 8:26 AM
The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.