More Code catastrophes uncovered and corrected in these faulty installations

Whoever performed this installation must not have even known that the NEC has rules for temporary wiring.

While it's true that, by necessity, the NEC rules for temporary wiring are not nearly as strict as those for permanent installations, there are still rules. One that's been violated here is the concern for “protection” of the conductors. Section 590.4(H) states, “Flexible cords and cables shall be protected from accidental damage. Sharp corners and projections shall be avoided. Where passing through doorways or other pinch points, protection shall be provided to avoid damage.”

Although that wording doesn't specifically prohibit the temporary wiring from being strung across this staircase, the basic requirement to essentially route and locate the cables so as to prevent damage has not been satisfied — therein lies the problem. It seems pretty clear that people traveling up and down those stairs are going to (at some point) come in contact with the cables and either pull the conductors apart or trip and injure themselves. A little bit of common sense can go a long way toward providing a safer working environment for job-site personnel, not to mention offering a modicum of legal protection for the installer.

Another problem is the means of support — or lack thereof. Part (J) of 590.4 says, “Cable assemblies and flexible cords shall be supported at intervals that ensure that they will be protected from physical damage. Support shall be in the form of staples, cable ties, straps or similar fittings installed so as to not cause damage. Vegetation shall not be used for support of overhead spans of branch circuits or feeders.”

In this case, the installer failed to support the conductors in manner that will prevent damage, which is a violation. In addition, although not visible, the installer used electrician's tape as a means of support. Tape is not specifically identified, and it doesn't seem to me that tape is a “similar fitting,” as required by the wording of this rule.

We know the wording of 90.3 provides guidelines on “which rules apply when.” As this section states, “This Code is divided into the introduction and nine chapters, as shown in Fig. 90.3. Chapters 1, 2, 3, and 4 apply generally; Chapters 5, 6, and 7 apply to special occupancies, special equipment, or other special conditions. These latter chapters supplement or modify the general rules. Chapters 1 though 4 apply except as amended by Chapter 5, 6, and 7.” With the foregoing in mind, one can immediately see that the rule of 110.12, “Mechanical Execution of Work,” must be satisfied. Here, the Code says, “Electrical equipment shall be installed in a neat and workmanlike manner.” No one in their right mind would characterize this knotted mess of cables as “neat and workmanlike.”


Want to use this article? Click here for options!





Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

Feb 2, 2012 7:54 PM

What's Wrong Here?

Jan 19, 2012 4:06 PM

What's Wrong Here?

Jan 5, 2012 11:53 AM

View all What's Wrong Here?

product spotlight

Labeling tool

Feb 10, 2012 7:58 AM

Labeling tool

The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M TV

Arlington CP9000

Arlington's new 9" diameter ceiling cover plate is the neatest way to cover unused "high hat" cans. With no tools needed, installation couldn't be faster!...

Arlington Gangable Boxes

Designed for new or retrofit applications, these snap-together gangable plastic boxes eliminate the need to construct a multiple-gang steel box out of several individual ones...

Understanding NEC Requirements for Solar Photovoltaic Systems
During this session, Mike Holt will address possible conflicts or confusing NEC requirements, provide tips on proper electrical installation techniques, and discuss the dangers related to improper installations. View this On Demand Webinar!



resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues