Illustrated Catastrophes
More Code catastrophes
As usual, never consider the following commentary associated with these photos as a formal interpretation of the National Electrical Code (NEC). Without criticizing anyone or any product, the following scenarios present us with serious safety questions.
All references are based on the 2005 NEC.
KEEP IT COOL
Thomas H. Ford, a partner of Bhamani, Ford & Associates, Inc., Miami, found these unique panels in a restaurant. “On the top of each panel an inline fan has been installed to provide ventilation for the interior of the panel,” says Ford. “This was done because the vestibule, where the panels are located, is so warm that the breakers would trip. The fans solved this problem, but created another. The kitchen air is so laden with cooking oil particulate that when it is forced into the panel the cooking oil settles on the interior components. After the gutter was installed, the walls were tiled, covering the left side of the panel. Screws hold the cover to the gutter. This now means the cover can't be removed.”
When you think about “conditions of use,” you must take into account the ampacity of the conductors (Art. 100) and make sure they don't exceed their temperature rating [110.14(C)]. You must do the same for the conductor terminations. It's hard to imagine the original installer addressed this in the initial design. But one thing is for sure: The practice of installing makeshift ventilation systems to minimize overheating problems should not be allowed or tolerated by anyone.
MOVE THE RECEPTACLE OR THE WALL?
Mark Gravill, a service technician with Gaylor in Phoenix, found this unique situation on the roof of a building. “I'd say either move the receptacle or move the wall,” says Gravill.
It's apparent that the electrician was here first, so the wall must go! I'm not sure of the circumstances at this specific location, but it looks like the right type of cover was used, and it's probably GFCI protected in accordance with 210.8 and 406.8(A) and (B).
Found a Code violation? E-mail your text and photos (no cell phone images please) to Joe Tedesco at
joetedesco@comcast.net
Want to use this article? Click here for options!
© 2012 Penton Business Media, Inc.
Latest Articles
Labeling tool
Feb 10, 2012 7:58 AM
Emergency lighting controls
Feb 9, 2012 8:40 AM
Cupertino Electric Sponsors Construction Industry Academic Competition
Feb 8, 2012 4:14 PM
Trending Articles
Acceptable Use Policy blog comments powered by Disqus
advertisement
product spotlight
Labeling tool
Feb 10, 2012 7:58 AM
The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.