Illustrated Catastrophes

Nov 1, 2008 12:00 PM, By Joe Tedesco, NEC Columnist

More Code catastrophes

As usual, never consider the following commentary associated with these photos as a formal interpretation of the National Electrical Code (NEC). Without criticizing anyone or any product, the following scenarios present us with serious safety questions.

All references are based on the 2008 NEC.

FILL 'ER UP

Jamie Conrad, a foreman/journeyman electrician with RJ Skelding Co., Inc., in Allentown, Pa., ran across this mess at a hotel. “The only wire feeding into the panel that is right is the one I added with an MC connector,” says Conrad. “The rest of the wires enter Romex connectors. Also, you can see they used a piece of broken plumbing pipe to run the feed and some branch circuits from a panel next to this panel.”

From the looks of this installation, it was never inspected. Aside from the improper use of fittings not designed for the wiring methods used here (300.15), we should also be reminded that plumbing materials do not comply with wiring method requirements in 110.8. Only wiring methods recognized as suitable are included in the NEC.



NO STANDING ZONE

Robert Lengfelder, senior program manager, RGLA Solutions, Inc., Schiller Park, Ill., ran across this 122.5kVA transformer at a job site. “After I commented, ‘I don't think that's safe,’ they reinforced the Unistrut to be supported from the other two bar joists as well,” says Lengfelder. “Notice how the Unistrut is bending. The transformer weighs approximately 800 pounds!”

Qualified persons and installers are trained to provide supporting methods that will be strong enough to hold the weight of the equipment. Obviously, these installers used no common sense here. The location of the equipment may comply with 450.13, but all bets are off until the metal framing supports are redesigned.

As per 450.13, “All transformers and transformer vaults shall be readily accessible to qualified personnel for inspection and maintenance or shall meet the requirements of 450.13(A) or 450.13(B).”

Found a Code violation? E-mail your photos (no cell phone images, please) to electrical.group@penton.com, and we'll try and publish them in a future issue.

Want to use this article? Click here for options!



Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

Nov 5, 2009 11:50 AM

What's Wrong Here?

Oct 22, 2009 11:16 PM

What's Wrong Here?

Oct 8, 2009 3:32 PM

View all What's Wrong Here?

product of the week

LED light engine

November 2, 2009

LED light engine

View all 2009 Products of the Week

Recent Comments

More...


EC&M TV

Exterior Fixture Box for Brick or Stone

Installing a fixture box in a brick or stone wall just got easier with Arlington’s new adjustable depth box!

Southwire's 2009 Cable Innovation Road Show

Gain years worth of insight in only 2-1/2 hours with Southwire’s 2009 Cable Innovation Road Show with Grounding Seminar. The agenda is packed with valuable information that focuses on installation tips!

Listen
Sizing Gen-Sets: Facts, Hints, and Good Judgment
Listen

The complexities of today’s commercial or industrial facility, with their equipment environment of linear and nonlinear loads, places a whole new light on sizing engine-generator sets.

Arc Mitigation - A Total System Approach
There’s no question the risk of arc flash hazards is real in the electrical industry. What many don’t always realize is the impact in business interruption from such events typically far outweighs the physical damage to equipment. View this On Demand Webinar!

Implementing an Industrial Ethernet Infrastructure that's Built to Last
This webinar explores the key benefits of implementing a robust complete, end-to-end Industrial Ethernet solution – from cabling and connectivity, to active components and associated hardware. View this On Demand Webinar!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues