Illustrated Catastrophes

Feb 1, 2008 12:00 PM, By Joe Tedesco, NEC Columnist

More Code catastrophes

As usual, never consider the following commentary associated with these photos as a formal interpretation of the National Electrical Code (NEC). Without criticizing anyone or any product, the following scenarios present us with serious safety questions.

All references are based on the 2008 NEC.


WANNABE ELECTRICIAN TURNED PLUMBER

Daryl Towne, a project manager with Total Electric, Inc., located in Wichita, Kan., ran across this when his team was remodeling a building. “The copper tubing was poured in the slab 30 years ago when the building was first built,” says Towne. “I guess they ran out of PVC and used what the plumber had on hand.”

The internal diameter of this kinky copper tubing may be found in the plumbing code, and could possibly be properly sized for these wires, as noted in Table 4 Dimensions and Percent Area of Conduit and Tubing (Areas of Conduit or Tubing for the Combinations of Wires Permitted in Table 1, Chapter 9 in the NEC).

However, this installation is in no way acceptable. It violates the requirements of 110.8, which states “Only wiring methods recognized as suitable are included in this Code. The recognized methods of wiring shall be permitted to be installed in any type of building or occupancy, except as otherwise provided in this Code.”








HUNG OUT TO DRY

Tom Bates, a student from Lancaster, Pa., ran across this unusual installation at a roadside farmers' market in Pennsylvania. “Where was the building inspector for this one,” says Bates.

This installation, once properly secured to the building, is now improperly supported because of the new siding job. There may be damaged service entrance conductors, raceway, fittings, enclosures, and feeders, etc. In my opinion, any new siding job should also include an electrical inspection. Some of the rules that are violated can be found in Art. 230 (Services), Art. 250 (Grounding and Bonding), and Art. 338 (Service-Entrance Cable). We could fill up this page with the appropriate section numbers.

Found a Code Violation? E-mail your photos (no cell phone images, please) to Joe Tedesco at joetedesco@comcast.net.

Want to use this article? Click here for options!



Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

Nov 5, 2009 11:50 AM

What's Wrong Here?

Oct 22, 2009 11:16 PM

What's Wrong Here?

Oct 8, 2009 3:32 PM

View all What's Wrong Here?

product of the week

Video camera scopes

November 16, 2009

Video camera scopes

View all 2009 Products of the Week

Recent Comments

More...


EC&M TV

Exterior Fixture Box for Brick or Stone

Installing a fixture box in a brick or stone wall just got easier with Arlington’s new adjustable depth box!

Southwire's 2009 Cable Innovation Road Show

Gain years worth of insight in only 2-1/2 hours with Southwire’s 2009 Cable Innovation Road Show with Grounding Seminar. The agenda is packed with valuable information that focuses on installation tips!

Listen
Sizing Gen-Sets: Facts, Hints, and Good Judgment
Listen

The complexities of today’s commercial or industrial facility, with their equipment environment of linear and nonlinear loads, places a whole new light on sizing engine-generator sets.

Arc Mitigation - A Total System Approach
There’s no question the risk of arc flash hazards is real in the electrical industry. What many don’t always realize is the impact in business interruption from such events typically far outweighs the physical damage to equipment. View this On Demand Webinar!

Implementing an Industrial Ethernet Infrastructure that's Built to Last
This webinar explores the key benefits of implementing a robust complete, end-to-end Industrial Ethernet solution – from cabling and connectivity, to active components and associated hardware. View this On Demand Webinar!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues