Illustrated Catastrophes

Feb 1, 2008 12:00 PM, By Joe Tedesco, NEC Columnist

More Code catastrophes


         Subscribe in NewsGator Online   Subscribe in Bloglines

As usual, never consider the following commentary associated with these photos as a formal interpretation of the National Electrical Code (NEC). Without criticizing anyone or any product, the following scenarios present us with serious safety questions.

All references are based on the 2008 NEC.


WANNABE ELECTRICIAN TURNED PLUMBER

Daryl Towne, a project manager with Total Electric, Inc., located in Wichita, Kan., ran across this when his team was remodeling a building. “The copper tubing was poured in the slab 30 years ago when the building was first built,” says Towne. “I guess they ran out of PVC and used what the plumber had on hand.”

The internal diameter of this kinky copper tubing may be found in the plumbing code, and could possibly be properly sized for these wires, as noted in Table 4 Dimensions and Percent Area of Conduit and Tubing (Areas of Conduit or Tubing for the Combinations of Wires Permitted in Table 1, Chapter 9 in the NEC).

However, this installation is in no way acceptable. It violates the requirements of 110.8, which states “Only wiring methods recognized as suitable are included in this Code. The recognized methods of wiring shall be permitted to be installed in any type of building or occupancy, except as otherwise provided in this Code.”








HUNG OUT TO DRY

Tom Bates, a student from Lancaster, Pa., ran across this unusual installation at a roadside farmers' market in Pennsylvania. “Where was the building inspector for this one,” says Bates.

This installation, once properly secured to the building, is now improperly supported because of the new siding job. There may be damaged service entrance conductors, raceway, fittings, enclosures, and feeders, etc. In my opinion, any new siding job should also include an electrical inspection. Some of the rules that are violated can be found in Art. 230 (Services), Art. 250 (Grounding and Bonding), and Art. 338 (Service-Entrance Cable). We could fill up this page with the appropriate section numbers.

Found a Code Violation? E-mail your photos (no cell phone images, please) to Joe Tedesco at joetedesco@comcast.net.

Want to use this article? Click here for options!

product of the week

Under cabinet luminaires

July 14, 2008 8:13 AM

View all 2008 Products of the Week

A panel of professionals answers your questions on a variety of topics.

I-Gard HRG and Arc Flash
I-Gard
Become an Expert
Submit your questions
iGard Resistance Grounding Q&A BookletDownload the Resistance Grounding Q&A Booklet
I-Gard

Learn how HRG technology can mitigate and reduce the arc flash hazard; design considerations to remember when specifying and installing an HRG system.
On-Demand Webinar
- Sponsored by I-Gard

Listen
"Full Voltage Motor Starting and Engine Generators"
Listen
Sponsored By:

 

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues