Mar 1, 2007 12:00 PM, By Joe Tedesco, NEC Columnist


         Subscribe in NewsGator Online   Subscribe in Bloglines     

As usual, never consider the following commentary associated with these photos as a formal interpretation of the National Electrical Code (NEC). Without criticizing anyone or any product, the following scenarios present us with serious safety questions.

All references are based on the 2005 NEC.

CARDBOARD BLANKS AND INVISIBLE INK

This is a problem I see all too often. How hard can it be to properly identify and label circuits? And who thinks cardboard is equivalent to a piece of metal when it comes to protection?

See 110.22, and the new 408.4, “Every circuit and circuit modification shall be legibly identified as to its clear, evident, and specific purpose or use. The identification shall include sufficient detail to allow each circuit to be distinguished from all others. The identification shall be included in a circuit directory that is located on the face or inside of the panel door in the case of a panelboard, and located at each switch on a switchboard.”

As per 408.7, “Unused openings for circuit breakers and switches shall be closed using identified closures, or other approved means that provide protection substantially equivalent to the wall of the enclosure.”

TWO-TONE PAINT JOB FOR CONDUITS?

This arrangement might have looked good when it was first installed, but someone forgot to think about the environmental conditions in which they were placing this equipment.

As noted in a portion of 110.11, “Unless identified for use in the operating environment, no conductors or equipment shall be located in damp or wet locations; where exposed to gases, fumes, vapors, liquids, or other agents that have a deteriorating effect on the conductors or equipment; or where exposed to excessive temperatures. FPN No. 1: See 300.6 for protection against corrosion.”

As per 300.6, “Raceways, cable trays, cable bus, auxiliary gutters, cable armor, boxes, cable sheathing, cabinets, elbows, couplings, fittings, supports, and support hardware shall be of materials suitable for the environment in which they are to be installed.”

More specific requirements for the protection of ferrous metal equipment, as shown in this photo, are noted in 300.6(A) and 300.6(A)(3).

Found a Code Violation? E-mail your photos to Joe Tedesco at joseph.tedesco@yahoo.com.


Commenting terms of use blog comments powered by Disqus

Want to use this article? Click here for options!

product of the week

Thermal imaging software

November 17, 2008 10:26 AM

Fluke SmartView Version 2.0

View all 2008 Products of the Week

Recent Comments

Follow comments on ecmweb.com




Arc Flash Conferences   Code Change Conferences

Professionals provide answers to your questions.



Do you have any technical paper explaining IBC?

iGard Resistance Grounding Q&A BookletDownload the Resistance Grounding Q&A Booklet
I-Gard
EC&M TV

Arlington Indoor InBox

Easy install makes Indoor InBox preferred for power & low voltage applications. Furniture and appliances stay close to the wall!...

Listen
"Sizing Gen-Sets: Facts, Hints, and Good Judgment"
Listen
Sponsored By:

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Back to Top

Browse Back Issues

Browse Back Issues