Sep 25, 2006 11:37 AM, By Steven Owen


         Subscribe in NewsGator Online   Subscribe in Bloglines     

Q. What is the minimum size XHHW insulated feeder conductor permitted for an industrial machine, which consists of the following loads? All terminals are rated at 75°C.

  • 10 each – 5 hp, 480VAC, 3-phase, squirrel-cage induction, continuous duty motors,
  • 10 each – 3 hp, 480VAC, 3-phase, squirrel-cage induction, continuous duty motors,
  • 10 each – 3kW, 480VAC, 1-phase, electric resistance heating loads,
  • 10 each – 2kW, 480VAC, 1-phase, electric resistance heating loads.
A) 3/0 AWG XHHW
B) 4/0 AWG XHHW
C) 250kcmil AWG XHHW
D) 300kcmil AWG XHHW

Answer: B

Explanation: Per Table 430.250, each of the 5 hp, 480VAC, 3-phase, squirrel-cage induction, continuous duty motors produces a full load current of 7.6A and each of the 3 hp, 480VAC, 3-phase, squirrel-cage induction, continuous duty motors produces a full load current of 4.8A.

Motors:
Largest motor (one of the 5hp motors) @ 1.25 (125% as per 670.4) = 7.6A X 1.25 = 9.5A
9 each, additional 5 hp motors X 7.6A = 68.4A
10 each, 3 hp motors X 4.8A = 48.0A
Subtotal = 125.9A

Resistance heating loads:
10 X 3kW = 30kW
10 X 2kW = 20kW
Subtotal = 50kW X 1.25 = 62.5kW
Convert 62.5kW to amperes – 62,500 ÷ (480V X 1.732) = 75.17A
Note: Even though the heating loads are single phase, the total heating load is supplied by a three-phase system.

Total = 125.9A + 75.17A = 201.07A; round down to 201A

The feeder conductors will be installed in one EMT raceway. The total number of conductors installed in the raceway is four. Three of the conductors are considered to be current carrying. Determine conductor size using XHHW insulated conductors. With no adjustments to make, (i.e., more than 3 current-carrying conductors in the EMT raceway, or ambient temperature exceeding 30°C), while also considering the 75°C terminals, we look at the 75°C column of Table 310.16 [based on terminal ratings – 110.14(C)]. A 4/0 AWG, XHHW insulated conductor is rated at 230A, from the 75°C column of Table 310.16. A 3/0 AWG, XHHW insulated conductor is rated at 200A, from the 75°C column of Table 310.16. However, it is one ampere short of the required 201A required.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at necexpert@aol.com.


Commenting terms of use blog comments powered by Disqus

Want to use this article? Click here for options!

product of the week

Evaluation Software

December 1, 2008 9:59 AM

Honeywell Power Evaluation Software

View all 2008 Products of the Week

Recent Comments

Follow comments on ecmweb.com




Arc Flash Conferences   Code Change Conferences

Professionals provide answers to your questions.



Do you have any technical paper explaining IBC?

iGard Resistance Grounding Q&A BookletDownload the Resistance Grounding Q&A Booklet
I-Gard
EC&M TV

Retrofit 2-Gang TV Box(TM)

Arlington’s recessed two-gang TV BOX™ for old work allows you to mount LCD and plasma TVs, and other system components flush against the wall.

Listen
"Sizing Gen-Sets: Facts, Hints, and Good Judgment"
Listen
Sponsored By:

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues