Code Quiz

Sep 23, 2004 11:01 AM, By Steven Owen


         Subscribe in NewsGator Online   Subscribe in Bloglines     

Imagine a metal junction box that is 32 inches x 32 inches x 6 inches with two 4-inch EMT raceways connected directly across from one another on opposite walls. Each 4-inch raceway contains three 250 kcmil conductors. An additional 2-inch EMT raceway, which contains three 4/0 AWG XHHW conductors, is connected to the back wall of the junction box directly opposite the removable cover, and another 2-inch EMT raceway has been connected to the bottom of the enclosure for a tap to a piece of industrial equipment. The 4/0 AWG conductors, which pass through the junction box, are installed in the 2-inch raceways. What's the minimum dimension required between either of the 4-inch raceways (installed in a horizontal position) and the 2-inch raceway connected to the bottom of the enclosure (installed in a vertical position)? Note: No conductors are installed between either of the 4-inch raceways or either of the 2-inch raceways.

A) 32 inches
B) 24 inches
C) 4 inches
D) No requirement for this installation

Answer: D)

Explanation: The following sentence located directly beneath the Exception to 314.28(A)(2) is seldom read, but its content is still important: “The distance between raceways enclosing the same conductor shall not be less than 6 times the trade diameter of the larger raceway.” This applies to angle or U-pulls, and it could be applied to 2-inch raceways, but not those in the question posed. In this example there’s no angle pull between the 4-inch raceway(s) and the 2-inch raceway(s), so this requirement doesn’t apply as the question is written.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states.


Acceptable Use Policy
blog comments powered by Disqus

Want to use this article? Click here for options!

what's wrong here?

What's Wrong Here?

Jul 2, 2009 6:51 PM

What's Wrong Here?

Jun 18, 2009 4:01 PM

What's Wrong Here?

Jun 4, 2009 1:26 PM

View all What's Wrong Here?

Recent Comments

Follow comments on ecmweb.com

i-Gard contest
Here’s your chance to win $5000! All you have to do is submit a case history based on your or your client’s experience (positive or negative) in applying HRG technology to an existing or new power distribution system.
EC&M White Papers
Protecting Generators through Hybrid Grounding
The industry has recently become aware of the problem of severe generator damage due to stator ground faults. Two factors have been identified as contributors to this growing problem
EC&M TV

Retrofit 2-Gang TV Box(TM)

Arlington’s recessed two-gang TV BOX™ for old work allows you to mount LCD and plasma TVs, and other system components flush against the wall...

Hybrid Grounding - The industry has recently become aware of the problem of severe generator damage due to stator ground faults. Join us for this live webinar!

Arc Flash HazardThe 3 As of Arc Flash - Awareness, Analysis, Action

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues