ECM Buyers' Guide
  

Code Quiz

Jun 23, 2005 9:01 AM, By Steve Owen

What’s the allowable ampacity of each of the current-carrying conductors of a 4-conductor, 2 AWG, type SO cord that’s rated 75° C by the manufacturer and connected to a 3-phase, 4-wire piece of equipment (no neutral load)? The conductors are installed in an area where the ambient temperature has been determined to be 50° C by a documented engineering study.

A) 60A
B) 71.25A
C) 72.80A
D) 86.45A

Answer: A)

Explanation: Per a change in the 2005 NEC, 400.5(A) was revised to allow for adjustment of current-carrying capacity (ampacity) of conductors when installed in areas where the ambient temperatures exceed the 30°C / 86°F, as described in the bold print header of Table 310.16.

The ampacity adjustments from the adjustment table on the bottom of Table 310.16 are almost always reduced to lower values than the initial values established in Tables 400.5(A) and (B) or the ampacities of Tables 310.16-19.

The adjustment factors beneath Table 310.16 shall be applied as stated in this explanation.

The ampacity for a 2 AWG Type SO cord (3-phase, 4-wire application, 3-current-carrying conductors) is 80A, as listed in Table 400.5(A), Column A. The correction factor for an ambient temperature of 50°C / 122°F, as noted in the bottom of Table 310.16 is 0.75 (from the 75°C column, based on the manufacturer's 75°C rating of the type SO cord).

Therefore, the allowable ampacity under the conditions specified in this question would be 80A × 0.75 = 60A.

Note: This doesn’t address terminations, only the allowable ampacity under the specified conditions.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at necexpert@aol.com.

Want to use this article? Click here for options!



Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

Nov 5, 2009 11:50 AM

What's Wrong Here?

Oct 22, 2009 11:16 PM

What's Wrong Here?

Oct 8, 2009 3:32 PM

View all What's Wrong Here?

product of the week

LED light engine

November 2, 2009

LED light engine

View all 2009 Products of the Week

Recent Comments

More...


EC&M TV

Exterior Fixture Box for Brick or Stone

Installing a fixture box in a brick or stone wall just got easier with Arlington’s new adjustable depth box!

Southwire's 2009 Cable Innovation Road Show

Gain years worth of insight in only 2-1/2 hours with Southwire’s 2009 Cable Innovation Road Show with Grounding Seminar. The agenda is packed with valuable information that focuses on installation tips!

Listen
Sizing Gen-Sets: Facts, Hints, and Good Judgment
Listen

The complexities of today’s commercial or industrial facility, with their equipment environment of linear and nonlinear loads, places a whole new light on sizing engine-generator sets.

Arc Mitigation - A Total System Approach
There’s no question the risk of arc flash hazards is real in the electrical industry. What many don’t always realize is the impact in business interruption from such events typically far outweighs the physical damage to equipment. View this On Demand Webinar!

Implementing an Industrial Ethernet Infrastructure that's Built to Last
This webinar explores the key benefits of implementing a robust complete, end-to-end Industrial Ethernet solution – from cabling and connectivity, to active components and associated hardware. View this On Demand Webinar!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues