ECM Buyers' Guide

Code Quiz

May 21, 2004 12:00 PM, By Steven Owen


         Subscribe in NewsGator Online   Subscribe in Bloglines     

Q. Two 480V motor control centers (MCCs) are located directly across the aisle from one another and face each other in an electrical distribution room. They’re exactly 48 inches apart, which complies with Table 110.26(A)(1) for a Condition 3 spacing requirement. One of the existing MCCs is set to be replaced with a new MCC that’s 5 inches deeper, but the existing MCC is set against a wall, so the new MCC will have to be installed in the exact location. This will cause the new MCC to extend 5 inches into the required working space between the two MCCs. The proposed installation will allow 43 inches between the MCCs (front-to-front). What is the minimum spacing required for this proposed installation to be Code compliant?

A) 48 inches
B) 43 inches
C) 42 inches
D) 36 inches

Answer: C

Explanation: In 110.26(A)(1)(c), the 2002 NEC permits a reduction of 6 inches by re-classifying a Condition 3 space to a Condition 2 space. This is reducing a 48-inch minimum space to a 42-inch minimum space. This is allowable when conditions of maintenance and supervision ensure that written procedures have been adopted to prohibit equipment on both sides of the aisle from being open at the same time, and qualified persons who are authorized will service the installation.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states.


Acceptable Use Policy
blog comments powered by Disqus

Want to use this article? Click here for options!

what's wrong here?

What's Wrong Here?

Jul 2, 2009 6:51 PM

What's Wrong Here?

Jun 18, 2009 4:01 PM

What's Wrong Here?

Jun 4, 2009 1:26 PM

View all What's Wrong Here?

Recent Comments

Follow comments on ecmweb.com

i-Gard contest
Here’s your chance to win $5000! All you have to do is submit a case history based on your or your client’s experience (positive or negative) in applying HRG technology to an existing or new power distribution system.
EC&M White Papers
Protecting Generators through Hybrid Grounding
The industry has recently become aware of the problem of severe generator damage due to stator ground faults. Two factors have been identified as contributors to this growing problem
EC&M TV

Retrofit 2-Gang TV Box(TM)

Arlington’s recessed two-gang TV BOX™ for old work allows you to mount LCD and plasma TVs, and other system components flush against the wall...

Hybrid Grounding - The industry has recently become aware of the problem of severe generator damage due to stator ground faults. Join us for this live webinar!

Arc Flash HazardThe 3 As of Arc Flash - Awareness, Analysis, Action

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues