Code Quiz

Q. A contractor installed a 2,000A, 480V, 3-phase feeder in six separate raceways, consisting of a total of six 500kcmil XHHW insulated conductors per phase. Four of the raceways are 3-inch trade size EMT. The other two raceways are 3˝-inch RMC. All conductors are exactly the same length, per paralleled phase, and feature the same insulation type and conductor material. In addition, all are terminated in the same manner and have the same cross-sectional area. The inspector has turned this installation down. What could possibility make this installation non-Code compliant?

    1. Nothing. This installation is Code compliant.
    2. The raceways are not the same. You must change all raceway sizes to either 3˝-inch EMT or 3˝-inch RMC.
    3. The raceways are not the same. You must change all raceways to either EMT or RMC of the proper trade size.
    4. The installation has an incorrect number of conductors paralleled. Change the number of conductors per phase from six to five.
Answer: C

Where run in separate raceways or cables, the raceways or cables shall have the same physical characteristics (i.e., same type conduit) [310.4]. In addition, the installation shall meet these five requirements:

    1. All conductors shall be exactly the same length per paralleled phase.
    2. All conductors shall have the same insulation type.
    3. All conductors shall be made of the same material.
    4. All conductors shall have the same cross-sectional area.
    5. All conductors shall be terminated in the same manner.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at necexpert@aol.com.


Want to use this article? Click here for options!





Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

Feb 2, 2012 7:54 PM

What's Wrong Here?

Jan 19, 2012 4:06 PM

What's Wrong Here?

Jan 5, 2012 11:53 AM

View all What's Wrong Here?

product spotlight

Emergency lighting controls

Feb 9, 2012 8:40 AM

Emergency lighting controls

The UL924 emergency lighting control relay (ERC) mounts in the ceiling and features an automatic diagnostic feature ...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M TV

Arlington CP9000

Arlington's new 9" diameter ceiling cover plate is the neatest way to cover unused "high hat" cans. With no tools needed, installation couldn't be faster!...

Arlington Gangable Boxes

Designed for new or retrofit applications, these snap-together gangable plastic boxes eliminate the need to construct a multiple-gang steel box out of several individual ones...

Understanding NEC Requirements for Solar Photovoltaic Systems
During this session, Mike Holt will address possible conflicts or confusing NEC requirements, provide tips on proper electrical installation techniques, and discuss the dangers related to improper installations. View this On Demand Webinar!



resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues