Consider the following situation: Three black 12 AWG THHN conductors pass directly through a box, uncut and unspliced. Three red 12 AWG THHN conductors are looped in the box. The loop measures 12 inches for each conductor. Six white (grounded) conductors are also looped with 12-inch loops. As would be expected, a green 12 AWG equipment grounding conductor originates at the panelboard and is installed with the branch-circuit conductors, cut into two pieces (each measuring 6 inches) within the box. An equipment bonding jumper is also pigtailed within the box (to the equipment grounding conductors), bonding the equipment grounding conductors to the box, but it doesn’t leave the box. What’s the minimum cubic inch capacity for the box?

A) 29.25 cu. in.
B) 31.50 cu. in.
C) 33.75 cu. in.
D) 49.50 cu. in.

Answer: D)

Per a 2005 NEC change, 314.16(B)(1) was revised to address looping of conductors within boxes. If the looped conductor measures 12 inches or more on its exposed length within the box, with reference to section 300.14, each looped conductor will now be considered to be two conductors. As has been the case for some time, a conductor that passes through the box, uncut, unspliced, and not looped 12 inches or more counts as only one conductor. Any conductor that is cut is counted as two conductors. One or more equipment grounding conductors count only as one conductor.

To find the mimimum size in cubic inches of a box for this application, you have to perform the following calculations:

Three black 12 AWG THHN conductors at 2.25 cubic inches each per 314.16(B).
2.25 X 3 = 6.75 cu. in. (uncut, unspliced)

Three red 12 AWG THHN conductors at 2.25 cubic inches each per 314.16(B).
2.25 X 3 X 2 = 13.5 cu. in. (because of the loop)

Six white 12 AWG THHN conductors at 2.25 cubic inches each per 314.16(B).
6 X 2.25 X 2 = 27 cu. in. (because of the loop)

Two green 12 AWG THHN conductors at 2.25 cubic inches each per 314.16(B).
2.25 X 1 = 2.25 cu. in. (because equipment grounding conductors count only as one)

One green 12 AWG THHN pigtail equipment bonding conductor, which originates in the box and doesn’t leave the box does not count.

Minimum box size:
6.75 + 13.5 + 27 + 2.25 = 49.5 cu. in.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at necexpert@aol.com.


Commenting terms of use blog comments powered by Disqus

Want to use this article? Click here for options!

product of the week

Evaluation Software

December 1, 2008 9:59 AM

Honeywell Power Evaluation Software

View all 2008 Products of the Week

Recent Comments

Follow comments on ecmweb.com




Arc Flash Conferences   Code Change Conferences

Professionals provide answers to your questions.



Do you have any technical paper explaining IBC?

iGard Resistance Grounding Q&A BookletDownload the Resistance Grounding Q&A Booklet
I-Gard
EC&M TV

Retrofit 2-Gang TV Box(TM)

Arlington’s recessed two-gang TV BOX™ for old work allows you to mount LCD and plasma TVs, and other system components flush against the wall.

Listen
"Sizing Gen-Sets: Facts, Hints, and Good Judgment"
Listen
Sponsored By:

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues