Q. A new Design E motor has been chosen to replace an existing 480V, 50-hp, 3–phase AC motor. The existing motor was fed from an existing size 3 motor starter (controller) located in an existing motor control center. When is it permissible to use the existing size 3 starter (controller), which is in very good condition, for this new Design E motor, which is also 50-hp, 480V, 3-phase?

A) when the controller is rated as Type 2.
B) only when the motor control center is 10 years or older
C) any time
D) in general, it isn't permitted at any time to use the same size starter (controller) for a Design E motor.

Answer: D

Explanation: This was a 1996 NEC change to Section 430-83(a)(Ex)(1). A controller for a Design E motor rated more than 2 hp shall comply with a. or b. below:

a. It shall be marked as rated for use with a Design E motor. (I am not aware of any manufacturers who manufactured Design E controllers).
b. It shall have a horsepower rating not less than 1.4 times the rating of a motor rated 3 through 100 hp, or not less than 1.3 times the rating of a motor rated over 100 hp. For this application, a standard controller may be used if it is sized as such: 1.4 X 50 hp = 70 hp rating. A 70-hp rating is consistent with a size 4 controller (480VAC) for this application, which would be the minimum size required for this application.

The same rule still applies in the 2002 NEC in Section 430.83(A)(1).

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states.


Acceptable Use Policy
blog comments powered by Disqus

Want to use this article? Click here for options!

what's wrong here?

What's Wrong Here?

Jul 2, 2009 6:51 PM

What's Wrong Here?

Jun 18, 2009 4:01 PM

What's Wrong Here?

Jun 4, 2009 1:26 PM

View all What's Wrong Here?

Recent Comments

Follow comments on ecmweb.com

i-Gard contest
Here’s your chance to win $5000! All you have to do is submit a case history based on your or your client’s experience (positive or negative) in applying HRG technology to an existing or new power distribution system.
EC&M White Papers
Protecting Generators through Hybrid Grounding
The industry has recently become aware of the problem of severe generator damage due to stator ground faults. Two factors have been identified as contributors to this growing problem
EC&M TV

Retrofit 2-Gang TV Box(TM)

Arlington’s recessed two-gang TV BOX™ for old work allows you to mount LCD and plasma TVs, and other system components flush against the wall...

Hybrid Grounding - The industry has recently become aware of the problem of severe generator damage due to stator ground faults. Join us for this live webinar!

Arc Flash HazardThe 3 As of Arc Flash - Awareness, Analysis, Action

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues