Feb 1, 2001 12:00 PM, By James Stallcup, Jr., NEC and OSHA Consultant

Choose the best answer:

1. What size nonfused disconnect are you required to install for an air-conditioning unit with a compressor rated at 29A and a condenser rated at 2.5A?

(a) 20A (b) 30A (c) 60A (d) 100A

2. What size horsepower-rated disconnect are you required to install for an air-conditioning unit with a compressor rated at 29A and a condenser rated at 2.5A with a locked-rotor current rating (LRA) of 180A? (Note that the supply is 480V, 3-phase.)

(a) 25 hp (b) 30 hp (c) 40 hp (d) 50 hp

3. What size horsepower-rated disconnect are you required to install for the following loads on a 3-phase, 230V system?

• A/C unit with a compressor rated at 29A with a 200A LRA

• A/C unit with a compressor rated at 24A with a 150A LRA

• A/C unit with a compressor rated at 20A with a 140A LRA

(a) 20 hp

(b) 30 hp

(c) 35 hp

(d) 40 hp

4. What size disconnecting means (in horsepower) is required to disconnect the following loads on a 3-phase, 230V system?

• Motor rated at 38A with a 212A LRA

• A/C unit with a compressor rated at 28A with a 160A LRA

• A/C unit with a compressor rated at 24A with a 160A LRA

(a) 15 hp

(b) 20 hp

(c) 30 hp

(d) 35 hp

5. A cord-and-plug device may serve as the disconnecting means for a room air conditioner if it operates at:

(a) 120V or less

(b) 150V or less

(c) 250V or less

(d) 300V or less

Answers and Discussion:

1. (c), 60A. You must size the disconnect based on the full-load current rating of the nameplate or the nameplate branch-circuit selection current of the compressor, whichever is greater. The multiplier is 115%.

[29A + 2.5A] × 115 = 436.2A

36.2A requires a 60A disconnect

Stallcup’s Code Loop: Secs. 440-12(a)(1) and 240-6(a).

2. (a), 25 hp. When working with nameplate amperage ratings or branch-circuit current ratings instead of horsepower ratings, you must select the horsepower amperage rating from Tables 430-147 through 430-150. If the nameplate fails to list the LRA rating of the motor, you must select the horsepower amperage rating from Tables 430-151(A) and (B).

31.5 FLA requires 25 hp

180 LRA requires 25 hp

Stallcup’s Code Loop: Sec. 440-12(a)(2), Tables 430-150 and 430-151(B).

3. (c), 35 hp. Same explanation as in answer 2.

The disconnecting means must be rated at 35 hp.

Stallcup’s Code Loop: Sec. 440-12(b), Tables 430-150 and 430-151(B).

4. (d), 35 hp. When working with two or more hermetic motors or combination loads (such as hermetic motor loads, standard motor loads, and other loads), you must separate your totals to determine the rating of a single disconnecting means.

Therefore, the disconnecting means is required to be rated at 35 hp.

Stallcup’s Code Loop: Sec. 440-12(b)(2), Tables 430-150 and 430-151(B).

5. (c), 250V or less. A cord-and-plug device may serve as the disconnecting means for a room air conditioner if it operates at 250V or less, its controls are manually operated, it’s located within 6 ft of the floor, and it’s accessible to the user.

Find More Code Quizzes »

Want to use this article? Click here for options!




Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

Whats Wrong Here?

Mar 11, 2010 12:54 PM

What's Wrong Here?

Feb 18, 2010 5:04 PM

What's Wrong Here?

Feb 4, 2010 5:06 PM

View all What's Wrong Here?

product of the week

CAD Software

March 15, 2010

CAD Software

View all 2010 Products of the Week

Shocking Stats

54
More Industry Statistics

Recent Comments

More...




Professionals provide answers to your questions. Become an expert!


EC&M TV

Arlington CED1 Entrance Hoods

The Scoop Series CED Entrance Plates and Hoods are reversible, non-metallic, single and two-gang versions...

Southwire's 2009 Cable Innovation Road Show

Gain years worth of insight with Southwire’s 2009 Cable Innovation Road Show with Grounding Seminar!

George Brown College

Online Tech Training – Electronics, PLC, and Robotics programs at George Brown College.

 

Listen
Sizing Gen-Sets: Facts, Hints, and Good Judgment
Listen

The complexities of today’s commercial or industrial facility, with their equipment environment of linear and nonlinear loads, places a whole new light on sizing engine-generator sets.

Arc Mitigation - A Total System Approach
There’s no question the risk of arc flash hazards is real in the electrical industry. What many don’t always realize is the impact in business interruption from such events typically far outweighs the physical damage to equipment. View this On Demand Webinar!

Implementing an Industrial Ethernet Infrastructure that's Built to Last
This webinar explores the key benefits of implementing a robust complete, end-to-end Industrial Ethernet solution – from cabling and connectivity, to active components and associated hardware. View this On Demand Webinar!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues