Choose the best answer. (Assume all conductors pulled through the conduits in Questions 1-5 are No. 4 and larger.)

1. What is the minimum length pull box required for a straight pull having a run of 2-in. conduit entering and leaving opposite walls of the box?

(a) 12 in.
(c) 16 in.
(b) 14 in.
(d) 18 in.

2. What is the minimum size pull box required for a straight pull having parallel runs of 2½-in., 2-in., and 1½-in. conduit entering and leaving opposite walls of the box?

(a) 14 in.
(c) 18 in.
(b) 16 in.
(d) 20 in.

3. What is the minimum size pull box required for an angle pull with a run of 2-in. conduit that enters the top left wall and leaves the bottom right wall of the box?

(a) 8 in. x 8 in.
(b) 12 in. x 12 in.
(c) 14 in. x 14 in.
(d) 16 in. x 16 in.

4. What is the minimum size pull box required for an angle pull with runs of 4-in., 3-in., and 2-in. conduit entering and leaving the box?

(a) 29 in. x 29 in.
(b) 30 in. x 30 in.
(c) 32 in. x 32 in.
(d) 36 in. x 36 in.

5. What is the minimum size pull box required for a U-pull having a run of 2-in. conduit?

(a) 10 in. x 10 in.
(b) 12 in. x 12 in.
(c) 14 in. x 14 in.
(d) 16 in. x 16 in.

Answers and Discussion

1. (c). When sizing a pull box for a straight pull (conduits on opposite walls), multiply the dimension of the largest size conduit entering and leaving the box by a specified multiplier.

Step 1: Find the appropriate multiplier in Sec. 370-28(a)(1).

Multiplier = 8

Step 2: Calculate the required length.

2 in. x 8 = 16 in.

Solution: The minimum length of the pull box is 16 in.

Stallcup’s Code Loop: Sec. 370-28(a) and 370-28(a)(1).

2. (d). Junction boxes with more than two conduits connected to their sides (to form a straight pull) are sized by multiplying the trade diameter of the largest raceway by a specified multiplier. The dimensions of the remaining conduits do not factor into this calculation.

Step 1: Find the appropriate multiplier in Sec. 370-28(a)(1).

Multiplier = 8

Step 2: Calculate the required length.

2½ in. x 8 = 20 in.

Solution: The minimum length of the pull box is 20 in.

Stallcup’s Code Loop: Sec. 370-28(a) and 370-28(a)(1).

3. (b). When sizing a pull box for an angle pull, multiply the trade diameter of the largest conduit entering and leaving by a specified multiplier.

Step 1: Find the appropriate multiplier in Sec. 370-28(a)(2).

Multiplier = 6

Step 2: Calculate the required length.

2 in. x 6 = 12 in.

Solution: The minimum dimension of the pull box is 12 in. x 12 in.

Stallcup’s Code Loop: Sec. 370-28 and 370-28(a)(2).

4. (a). Junction boxes with more than one run of conduit connected to their walls to form an angle pull are sized by multiplying the trade diameter of the largest conduit by a specified multiplier and adding the dimensions of the remaining conduits to this value.

Step 1: Find the appropriate multiplier in Sec. 370-28(a)(2).

Multiplier = 6

Step 2: Calculate the required length.

4 in. x 6 = 24 in.

Step 3: Now add the diameters of the remaining conduits.

24 in. + 3 in. + 2 in. = 29 in.

Solution: The minimum dimension of the pull box is 29 in. x 29 in.

Stallcup’s Code Loop: Sec. 370-28 and 370-28(a)(2)

5. (b). Junction boxes with more than one run of conduit connected to their walls to form a U-pull are sized by multiplying the trade diameter of the largest conduit by a specified multiplier and adding the dimensions of the remaining conduits to this value.

Step 1: Find the appropriate multiplier in Sec. 370-28(a)(2).

Multiplier = 6

Step 2: Calculate the required length.

2 in. x 6 = 12 in.

Solution: The minimum dimension of the pull box is 12 in. x 12 in.

Stallcup’s Code Loop: Sec. 370-28(a) and 370-28(a)(2).

Find More Code Quizzes »


Want to use this article? Click here for options!





Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

Feb 2, 2012 7:54 PM

What's Wrong Here?

Jan 19, 2012 4:06 PM

What's Wrong Here?

Jan 5, 2012 11:53 AM

View all What's Wrong Here?

product spotlight

Labeling tool

Feb 10, 2012 7:58 AM

Labeling tool

The Rhino 4200 labeling tool features one-touch “hot keys” that quickly create and format wire/cable wraps, flags, fixed-length labels and more...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M TV

Arlington CP9000

Arlington's new 9" diameter ceiling cover plate is the neatest way to cover unused "high hat" cans. With no tools needed, installation couldn't be faster!...

Arlington Gangable Boxes

Designed for new or retrofit applications, these snap-together gangable plastic boxes eliminate the need to construct a multiple-gang steel box out of several individual ones...

Understanding NEC Requirements for Solar Photovoltaic Systems
During this session, Mike Holt will address possible conflicts or confusing NEC requirements, provide tips on proper electrical installation techniques, and discuss the dangers related to improper installations. View this On Demand Webinar!



resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues