Sep 1, 2000 12:00 PM, By James Stallcup, Jr.

Sizing Pull Boxes — Art. 370

Choose the best answer. (Assume all conductors pulled through the conduits in Questions 1-5 are No. 4 and larger.)

1. What is the minimum length pull box required for a straight pull having a run of 2-in. conduit entering and leaving opposite walls of the box?

(a) 12 in.
(c) 16 in.
(b) 14 in.
(d) 18 in.

2. What is the minimum size pull box required for a straight pull having parallel runs of 2½-in., 2-in., and 1½-in. conduit entering and leaving opposite walls of the box?

(a) 14 in.
(c) 18 in.
(b) 16 in.
(d) 20 in.

3. What is the minimum size pull box required for an angle pull with a run of 2-in. conduit that enters the top left wall and leaves the bottom right wall of the box?

(a) 8 in. x 8 in.
(b) 12 in. x 12 in.
(c) 14 in. x 14 in.
(d) 16 in. x 16 in.

4. What is the minimum size pull box required for an angle pull with runs of 4-in., 3-in., and 2-in. conduit entering and leaving the box?

(a) 29 in. x 29 in.
(b) 30 in. x 30 in.
(c) 32 in. x 32 in.
(d) 36 in. x 36 in.

5. What is the minimum size pull box required for a U-pull having a run of 2-in. conduit?

(a) 10 in. x 10 in.
(b) 12 in. x 12 in.
(c) 14 in. x 14 in.
(d) 16 in. x 16 in.

Answers and Discussion

1. (c). When sizing a pull box for a straight pull (conduits on opposite walls), multiply the dimension of the largest size conduit entering and leaving the box by a specified multiplier.

Step 1: Find the appropriate multiplier in Sec. 370-28(a)(1).

Multiplier = 8

Step 2: Calculate the required length.

2 in. x 8 = 16 in.

Solution: The minimum length of the pull box is 16 in.

Stallcup’s Code Loop: Sec. 370-28(a) and 370-28(a)(1).

2. (d). Junction boxes with more than two conduits connected to their sides (to form a straight pull) are sized by multiplying the trade diameter of the largest raceway by a specified multiplier. The dimensions of the remaining conduits do not factor into this calculation.

Step 1: Find the appropriate multiplier in Sec. 370-28(a)(1).

Multiplier = 8

Step 2: Calculate the required length.

2½ in. x 8 = 20 in.

Solution: The minimum length of the pull box is 20 in.

Stallcup’s Code Loop: Sec. 370-28(a) and 370-28(a)(1).

3. (b). When sizing a pull box for an angle pull, multiply the trade diameter of the largest conduit entering and leaving by a specified multiplier.

Step 1: Find the appropriate multiplier in Sec. 370-28(a)(2).

Multiplier = 6

Step 2: Calculate the required length.

2 in. x 6 = 12 in.

Solution: The minimum dimension of the pull box is 12 in. x 12 in.

Stallcup’s Code Loop: Sec. 370-28 and 370-28(a)(2).

4. (a). Junction boxes with more than one run of conduit connected to their walls to form an angle pull are sized by multiplying the trade diameter of the largest conduit by a specified multiplier and adding the dimensions of the remaining conduits to this value.

Step 1: Find the appropriate multiplier in Sec. 370-28(a)(2).

Multiplier = 6

Step 2: Calculate the required length.

4 in. x 6 = 24 in.

Step 3: Now add the diameters of the remaining conduits.

24 in. + 3 in. + 2 in. = 29 in.

Solution: The minimum dimension of the pull box is 29 in. x 29 in.

Stallcup’s Code Loop: Sec. 370-28 and 370-28(a)(2)

5. (b). Junction boxes with more than one run of conduit connected to their walls to form a U-pull are sized by multiplying the trade diameter of the largest conduit by a specified multiplier and adding the dimensions of the remaining conduits to this value.

Step 1: Find the appropriate multiplier in Sec. 370-28(a)(2).

Multiplier = 6

Step 2: Calculate the required length.

2 in. x 6 = 12 in.

Solution: The minimum dimension of the pull box is 12 in. x 12 in.

Stallcup’s Code Loop: Sec. 370-28(a) and 370-28(a)(2).

Find More Code Quizzes »

Want to use this article? Click here for options!




Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

Whats Wrong Here?

Mar 11, 2010 12:54 PM

What's Wrong Here?

Feb 18, 2010 5:04 PM

What's Wrong Here?

Feb 4, 2010 5:06 PM

View all What's Wrong Here?

product of the week

CAD Software

March 15, 2010

CAD Software

View all 2010 Products of the Week

Shocking Stats

54
More Industry Statistics

Recent Comments

More...




Professionals provide answers to your questions. Become an expert!


EC&M TV

Arlington CED1 Entrance Hoods

The Scoop Series CED Entrance Plates and Hoods are reversible, non-metallic, single and two-gang versions...

Southwire's 2009 Cable Innovation Road Show

Gain years worth of insight with Southwire’s 2009 Cable Innovation Road Show with Grounding Seminar!

George Brown College

Online Tech Training – Electronics, PLC, and Robotics programs at George Brown College.

 

Listen
Sizing Gen-Sets: Facts, Hints, and Good Judgment
Listen

The complexities of today’s commercial or industrial facility, with their equipment environment of linear and nonlinear loads, places a whole new light on sizing engine-generator sets.

Arc Mitigation - A Total System Approach
There’s no question the risk of arc flash hazards is real in the electrical industry. What many don’t always realize is the impact in business interruption from such events typically far outweighs the physical damage to equipment. View this On Demand Webinar!

Implementing an Industrial Ethernet Infrastructure that's Built to Last
This webinar explores the key benefits of implementing a robust complete, end-to-end Industrial Ethernet solution – from cabling and connectivity, to active components and associated hardware. View this On Demand Webinar!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues