Quizzes on the Code

Choose the best answer:

  1. The requirements in Art. 511 apply to locations intended for service and repair operations in connection with self-propelled vehicles like ____, in which volatile flammable liquids or flammable gases are used for fuel or power.
    (a) buses
    (b) trucks
    (c) tractors
    (d) all of these

  2. You must follow the requirements of Art. 514 when installing the wiring in areas used for motor fuel dispensers or areas in which flammable fuel is transferred to vehicle fuel tanks.
    (a) true
    (b) false

  3. The service and repair area up to ___ in. above the floor shall be classified as Class I, Division 2.
    (a) 6
    (b) 12
    (c) 18
    (d) 24

  4. The area within ___ in. of the ceiling in locations where compressed natural gas (CNG) vehicles are repaired or stored must be classified as Class I, Division 2, except where ventilation of at least four air changes per hour is provided.
    (a) 6
    (b) 12
    (c) 18
    (d) 24

  5. Any pit or depression below the service and repair floor shall be considered a Class I, Division 1 location.
    (a) true
    (b) false

  6. If you're installing wiring or equipment within a Class I location, you must run the wires in threaded rigid metal or intermediate metal conduit. But if the installation requires you to run the wiring underground, you can use rigid nonmetallic conduit (RNC) with an equipment grounding conductor if it has at least ___ ft of cover.
    (a) 1
    (b) 2
    (c) 3
    (d) none of these

  7. Lampholders and lamps for fixed lighting over travel lanes or where exposed to physical damage must be more than 12 ft above floor level, unless the luminaires are completely enclosed or are constructed to prevent sparks or hot metal particles from escaping.
    (a) true
    (b) false

  8. The NEC requires GFCI protection for all 125V single-phase 15A and 20A receptacles used for service and repair operations like electrical automotive diagnostic equipment, electrical hand-tools, and portable lighting devices.
    (a) true
    (b) false




Answers and Discussion

  1. (d), all of these

    Although Art. 511 covers service and repair garages for these vehicles, it doesn't apply to residential garages or repair shops for watercraft, 4-wheelers, or motorcycles.

  2. (a), true

    It's possible for an establishment to have a vehicle service and repair area that must comply with Art. 511, another area for fuel dispensing that must comply with Art. 514, and other areas, such as show rooms, offices, or a parts department, that must comply with Chapters 1 through 4.

  3. (c), 18.

    The only exception to 511.3(B)1 is when the enforcing agency determines that mechanical ventilation is providing a minimum of four air changes per hour or 1 cu ft per min of exchanged air for each square foot of floor area. The ventilation system must provide for air exchange across the entire floor area within 12 in. of the floor.

  4. (c), 18

    Per 511.3(B)(2).

  5. (a), true

    There are two exceptions to 511.3(B)(3). The first states, “any pit or depression in which six air changes per hour are exhausted at the floor level of the pit shall be permitted to be judged by the enforcing agency to be a Class I, Division 2 location.” The second states, “lubrication and service rooms without dispensing shall be classified in accordance with Table 514.3(B)(1).”

  6. (b), 2

    An Exception to 511.4(A)(1) for RNC stipulates that if the raceway enters a classified location, the underfloor area takes on the classification of the above area, even if the conduit passes unbroken through the classified area and terminates in an unclassified area. The concern is volatile gas seepage into the underfloor area through the conduit openings in the floor.

  7. (a), true

    Per 511.7(B)(1)(b).

  8. (a), true

    Per 511.12.

Are you still confused by the Code? For additional information on Code-related topics please visit www.mikeholt.com or send an e-mail directly to the author at mike@mikeholt.com.

Find More Code Quizzes »






Acceptable Use Policy
blog comments powered by Disqus

what's wrong here?

What's Wrong Here?

May 10, 2012 12:44 PM

What's Wrong Here?

Apr 19, 2012 10:09 AM

What's Wrong Here?

Apr 5, 2012 2:27 PM

View all What's Wrong Here?

product spotlight

EV charger tester

May 25, 2012 8:26 AM

EV charger tester

The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...

View all 2012 Product Spotlights

Free Product Info

Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.

Recent Comments

More...


Social Media

More ways to stay informed...

follow us on twitter

Find us on Facebook

EC&M Whitepaper

Arc Mitigation –A Three-Step Approach

Did you know that an arc-flash incident hospitalizes 5-7 workers per day in North America, severely impacting processes and profitability with lost production? Download This Sponsored Whitepaper Today!

What's New in Residential Cabling?
Date: Wednesday, May 30, 2012
Time: 2:00pm ET


In this The Home Depot sponsored Low Voltage Webinar, Ron Kipper RCDD / NTS will discuss the need for compression style coaxial connectors and the migration of the entire CATV, Satellite and Audio / Video industry to them. Register Today!

Grounding Versus Bonding
Now Available On-Demand


In this 60-minute FREE webinar, Mike Holt of Mike Holt Enterprises, Inc. will explain the purpose of grounding and bonding as related to the most current requirements set forth in the 2011 NEC. Register to View On-Demand!

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

industry links

industry links

rss icon

rss

Browse Back Issues

Browse Back Issues