Q. What is the maximum allowable ampacity of a 10 AWG THHN or THWN-2 insulated conductor installed in a schedule 80 PVC raceway (90°C rated) installed underground from the branch-circuit panelboard to the luminaires installed for parking lot lighting? There are four current-carrying conductors in this raceway. Disregard the terminals and the branch-circuit rating for this example.

    1. 32A
    2. 30A
    3. 28A
    4. 24A

Answer: A

10 AWG THHN or THWN-2 is a 90°C rated conductor per Table 310.13(A). From Table 310.16, 90°C column, a 10 AWG THHN or THWN-2 is a 40A rated conductor at 30°C. Per 310.8, 10 AWG THHN or THWN-2 is permitted to be used in dry, dry and damp, and wet locations (the THWN-2 rating is used for wet locations).

40A x 0.8 (an adjustment factor for four current-carrying conductors [from 310.15(B)(2)(a)]) = 32A maximum allowable ampacity, per this set of conditions. We are not considering the terminals [(110.14 (C)] or the branch-circuit overcurrent protective device rating or setting at this time.

The answer is based on changes in the 2008 NEC [300.5(B), 310.8, 310.13(A), 310.15(B)(2)(a), 310.16, 352.10, and 352.12]. Even though it has been known that conductors within raceways installed in wet location are considered to also be in a wet location, this change in the NEC makes that point clear.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at necexpert@aol.com.

Want to use this article? Click here for options!

product of the week

Battery backup system

June 30, 2008 8:10 AM

View all 2008 Products of the Week

A panel of professionals answers your questions on a variety of topics.

I-Gard HRG and Arc Flash
I-Gard
Become an Expert
Submit your questions

Learn how HRG technology can mitigate and reduce the arc flash hazard; design considerations to remember when specifying and installing an HRG system.
On-Demand Webinar
- Sponsored by I-Gard

Listen
"Full Voltage Motor Starting and Engine Generators"
Listen
Sponsored By:

 

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues