Q. A cable tray system has been installed to support service entrance conductors. The service entrance conductors consist of six sets of three-conductor 500kcmil interlocked armored cables installed in parallel in a single layer in the tray. An additional feeder, consisting of three sets of parallel three-conductor 500kcmil interlocked armored cables, has been installed in a single layer in the same cable tray. The cable tray is wide open (i.e., no barriers or dividers). Is this installation NEC compliant?

    1. Yes, because all cables are interlocked armored cables.
    2. No, because conductors other than service entrance conductors are not permitted in the same cable tray with service entrance conductors, unless a solid fixed barrier of a material compatible with the cable tray is installed to separate the service entrance conductors from the other conductors.
    3. No, because interlocked armored cables are not permitted to be used as service entrance conductors.
    4. No, because cable trays cannot be used to support service entrance conductors.

Answer: B

In general, you’re permitted to use cable trays to support service entrance conductors as long as other conductors are not placed in the same tray. The only time you’re permitted to place other conductors in a cable tray with service entrance conductors is if you equip the cable tray with a fixed barrier of a material compatible with the cable tray and physically separate the service entrance conductors from the other conductors. [230.44]

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at necexpert@aol.com.


Acceptable Use Policy
blog comments powered by Disqus

Want to use this article? Click here for options!

what's wrong here?

What's Wrong Here?

Jul 2, 2009 6:51 PM

What's Wrong Here?

Jun 18, 2009 4:01 PM

What's Wrong Here?

Jun 4, 2009 1:26 PM

View all What's Wrong Here?

Recent Comments

Follow comments on ecmweb.com

i-Gard contest
Here’s your chance to win $5000! All you have to do is submit a case history based on your or your client’s experience (positive or negative) in applying HRG technology to an existing or new power distribution system.
EC&M White Papers
Protecting Generators through Hybrid Grounding
The industry has recently become aware of the problem of severe generator damage due to stator ground faults. Two factors have been identified as contributors to this growing problem
EC&M TV

Retrofit 2-Gang TV Box(TM)

Arlington’s recessed two-gang TV BOX™ for old work allows you to mount LCD and plasma TVs, and other system components flush against the wall...

Hybrid Grounding - The industry has recently become aware of the problem of severe generator damage due to stator ground faults. Join us for this live webinar!

Arc Flash HazardThe 3 As of Arc Flash - Awareness, Analysis, Action

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues