Code Quiz
Q. When grounding the frames of metal-enclosed power switchgear, which of the following methods listed here is the only one that is permitted by the 2008 NEC?
- A 6 AWG equipment bonding jumper from a nearby effectively grounded steel column.
- A 6 AWG grounding electrode conductor connected to a driven ground rod adjacent to the equipment.
- GFPE protection (30mA trip setting).
- A properly sized equipment-grounding conductor.
Answer: D
Per a change in the 2008 edition of the Code [490.36], instead of the statement "frames of switchgear and control assemblies shall be grounded," it is clearly noted now that "frames of switchgear and control assemblies shall be connected to an equipment-grounding conductor, or where permitted, the grounded conductor."
Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at necexpert@aol.com.
Want to use this article? Click here for options!
© 2012 Penton Business Media, Inc.
Latest Articles
EV charger tester
May 25, 2012 8:26 AM
CFL/LED dimmer
May 24, 2012 8:48 AM
Load bank
May 23, 2012 9:33 AM
Trending Articles
Acceptable Use Policy blog comments powered by Disqus
advertisement
what's wrong here?
What's Wrong Here?
May 10, 2012 12:44 PM
View all What's Wrong Here?
What's Wrong Here
Sponsored By:
product spotlight
EV charger tester
May 25, 2012 8:26 AM
The Electrician is portable tester that verifies critical power and safety requirements of electric vehicle (EV) chargers...
View all 2012 Product Spotlights
Free Product Info
Our Product Information site is the ultimate online resource for products and services offered by Advertisers featured in our Magazine. This service is provided as a quick and easy way to request Product Information online. Get FREE product information now.