Sep 27, 2007 1:02 PM, By Steven Owen


         Subscribe in NewsGator Online   Subscribe in Bloglines     

Q. A 60-foot metal pole supporting luminaires is found to be deficient with respect to the 2005 version of the NEC. The installation consists of the following: The interior of the pole is being used as a raceway. A properly sized handhole has been provided. A grounding terminal within the pole has been provided. The size of the branch-circuit equipment-grounding conductor, which also serves to bond the metal pole to the metal raceway supporting the branch circuit conductors, is 12 AWG. The branch circuit rating is 30A.

What could possibly be the deficiency in this particular installation?

    1. There is no raceway inside the pole.
    2. The pole does not feature a hinged base.
    3. There is a lack of vertical conductor support per 300.19.
    4. Improperly sized equipment grounding and bonding conductor.

Answer: D

Per 410.15(B)(5), the size of the equipment and bonding jumper shall be in accordance with 250.122. A 30A rated branch circuit requires a minimum size 10 AWG equipment-grounding conductor.

Owen is the owner and president of National Code Seminars and the holder of master electrician certifications in 46 states. He can be reached at necexpert@aol.com.


Acceptable Use Policy
blog comments powered by Disqus

Want to use this article? Click here for options!

what's wrong here?

What's Wrong Here?

Jul 2, 2009 6:51 PM

What's Wrong Here?

Jun 18, 2009 4:01 PM

What's Wrong Here?

Jun 4, 2009 1:26 PM

View all What's Wrong Here?

Recent Comments

Follow comments on ecmweb.com

i-Gard contest
Here’s your chance to win $5000! All you have to do is submit a case history based on your or your client’s experience (positive or negative) in applying HRG technology to an existing or new power distribution system.
EC&M White Papers
Protecting Generators through Hybrid Grounding
The industry has recently become aware of the problem of severe generator damage due to stator ground faults. Two factors have been identified as contributors to this growing problem
EC&M TV

Retrofit 2-Gang TV Box(TM)

Arlington’s recessed two-gang TV BOX™ for old work allows you to mount LCD and plasma TVs, and other system components flush against the wall...

Hybrid Grounding - The industry has recently become aware of the problem of severe generator damage due to stator ground faults. Join us for this live webinar!

Arc Flash HazardThe 3 As of Arc Flash - Awareness, Analysis, Action

resources

product info icon

product info

tradeshow icon

tradeshow

research icon

research

rss icon

rss

Browse Back Issues

Browse Back Issues